{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6JQ32-0HA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6JQ32-0HA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6JQ32-0HA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JQ32-0HA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series molded case circuit breaker, 3VA2225-6JQ32-0HA0, 3-pole, 250 A rated continuous current, ETU560 electronic trip unit, line protection, 242 kA breaking capacity at 240 V.","salesMarkdown":"It carries a 242 kA breaking capacity at 240 V, stepping down to 187 kA at 415 V and 440 V, 121 kA at 500 V, and 6 kA at 690 V — so it handles high-fault-current service-entrance and distribution applications, not just motor branch circuits. The shunt-trip release (STL) is built in, letting you remotely trip the breaker from a safety circuit or emergency-stop chain. Dimensions are 86 mm deep, 105 mm wide, 181 mm tall — a standard 3-pole MCCB footprint that drops into SENTRON 3VA2 panelboards and most DIN-rail adapter plates.","metaTitle":"Siemens 3VA2225-6JQ32-0HA0 SENTRON MCCB, 250 A, 242 kA","metaDescription":"Siemens SENTRON 3VA2225-6JQ32-0HA0 molded case circuit breaker, 250 A rated current, 242 kA breaking capacity at 240 V. ETU560 trip unit, line protection. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"6 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"238 A","at 60 °C":"225 A","at 65 °C":"213 A","at 70 °C":"200 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"Yes","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"48 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"250 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2225-6JQ32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Summation current formation L-conductor","Of The Integrated Auxiliary Trip":"3VA9688-0BL30","Design of the overcurrent release":"ETU560","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"15","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"250 A","Adjustable response value current / lg max.":"250 A","Adjustable response value current / lg min.":"50 A","Adjustable response value current / li max.":"2 500 A","Adjustable response value current / li min.":"375 A","Adjustable response value current / lr min.":"100 A","Adjustable response value current / Isd max.":"2 500 A","Adjustable response value current / Isd min.":"150 A","Ground fault protection can be switched ON/OFF":"Yes","Neutral conductors / upgradeable/retrofittable":"Yes","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LSIG","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=452905&mlfb=3VA2225-6JQ32-0HA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JQ32-0HA0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCCB at different voltages?","answer":"242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 6 kA at 690 V."},{"question":"What trip unit does the 3VA2225-6JQ32-0HA0 use?","answer":"It uses the ETU560 electronic trip unit, which supports adjustable long-time, short-time, instantaneous, and ground-fault protection settings."},{"question":"Where can I buy the 3VA2225-6JQ32-0HA0?","answer":"This part is sourced to order through independent distribution. Submit an RFQ for current pricing and availability."},{"question":"Will the 3VA2225-6JQ32-0HA0 fit a panel designed for a 3VA1110-5EE32-0JA0?","answer":"No — the 3VA1110-5EE32-0JA0 is a 100 A frame MCCB with different dimensions and a lower interrupting rating. The 3VA2225-6JQ32-0HA0 uses the larger 250 A frame and will not drop into the same mounting footprint without panel modification."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6JQ32-0HA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6JQ32-0HA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}