{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6JQ32-0KH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6JQ32-0KH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6JQ32-0KH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JQ32-0KH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2, molded case circuit breaker, 3-pole, 250 A (40 °C), 242 kA at 240 V, line protection, with communication, shunt trip, 2 aux + 1 alarm switch.","salesMarkdown":"Breaking capacity reaches 242 kA at 240 V and stays at 187 kA through 440 V, then drops to 121 kA at 500 V and 4.5 kA at 690 V. The adjustable thermal-magnetic trip unit spans 375 A to 2500 A — the 250 A full-scale value is the frame rating, not the trip setting. Set the trip to match your downstream cable and load; the 2500 A maximum is for high-current tap protection or as a main in a sub-panel. The -6JQ32-0KH0 carries a shunt trip (STL) and a 2-auxiliary + 1-trip-alarm switch configuration. At 86 mm deep, 105 mm wide, and 181 mm tall, this 3-pole MCCB fits the standard SENTRON 3VA2 mounting footprint. The 105 mm width is the same across the 3VA2 frame up to 250 A, so a panel laid out for a 160 A 3VA2 accepts this 250 A unit without re-drilling the mounting plate. Maximum power loss is 48 W — relevant for enclosure thermal rise calculations in a sealed or high-fill panel. The basic switch order code is 3VA2225-6JQ32-0AA0 — that is the bare breaker without the plug-in electronic trip unit or communication module. The trip indicator is present and the voltage trigger is available — meaning the breaker can signal its tripped state and accept a remote trip command. No other measurement function is fitted; this is a protection device, not a power meter.","metaTitle":"Siemens 3VA2225-6JQ32-0KH0 SENTRON MCCB, 250 A, 242 kA","metaDescription":"Siemens 3VA2225-6JQ32-0KH0 SENTRON molded case circuit breaker, 3-pole, 250 A rated at 40 °C, 242 kA breaking at 240 V. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"2 500 A","Minimum":"375 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"238 A","at 60 °C":"225 A","at 65 °C":"213 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Initial Value":"50 A","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Full-Scale Value":"250 A","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"48 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2225-6JQ32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Summation current formation L-conductor","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU560","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"Yes","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSIG","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=286550&mlfb=3VA2225-6JQ32-0KH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6JQ32-0KH0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6JQ32-0KH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6JQ32-0KH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}