{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6KP32-0DC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6KP32-0DC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6KP32-0DC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6KP32-0DC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-6KP32-0DC0, molded case circuit breaker, 3-pole, 250 A at 40 °C, breaking capacity 242 kA at 240 V, line protection design with undervoltage release and communication function.","salesMarkdown":"The 3VA2225-6KP32-0DC0 is a Siemens SENTRON molded case circuit breaker (MCCB) rated for 250 A continuous current at 40 °C, with no derating needed up to 50 °C — the same 250 A holds across that range. The interrupting ratings climb with voltage: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 4.5 kA at 690 V — the 690 V figure is typical for a 250 A frame and confirms it handles low-level faults at that voltage but is not intended for high-fault 690 V mains. The 3-pole design is configured for line protection, with an undervoltage release fitted and a communication function for remote status. Maximum power loss is 50.5 W — factor that into panel thermal calculations. Dimensions are 105 mm wide, 181 mm high, 86 mm deep — a standard 3-pole MCCB footprint for 250 A frames.","metaTitle":"Siemens 3VA2225-6KP32-0DC0 SENTRON MCCB, 250 A, 3-Pole","metaDescription":"Siemens SENTRON 3VA2225-6KP32-0DC0 molded case circuit breaker, 250 A continuous, 3-pole, 242 kA at 240 V. Active production, sourced to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"2 500 A","Minimum":"375 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"238 A","at 60 °C":"225 A","at 65 °C":"213 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"50.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Of The Supplied Basic Switch":"3VA2225-6KP32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=34771&mlfb=3VA2225-6KP32-0DC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6KP32-0DC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2225-6KP32-0DC0 and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a quote request for current availability and pricing — no stock or price figures are published here."},{"question":"What are the key ratings of 3VA2225-6KP32-0DC0?","answer":"Continuous current 250 A at 40 °C, 3-pole, breaking capacity 242 kA at 240 V, 187 kA at 415 V, 187 kA at 440 V, 121 kA at 500 V, 4.5 kA at 690 V. Dimensions 105 x 181 x 86 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6KP32-0DC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6KP32-0DC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}