{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6KP32-0DL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6KP32-0DL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6KP32-0DL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6KP32-0DL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, molded case circuit breaker, 3VA2225-6KP32-0DL0, 250 A, 3-pole, 242 kA at 240 V, line protection with communication and undervoltage release.","salesMarkdown":"It delivers a breaking capacity of 242 kA at 240 V and 187 kA at 415 V, with derated performance at higher voltages down to 4.5 kA at 690 V. Above that, it derates linearly: 238 A at 55 °C, 225 A at 60 °C, 213 A at 65 °C, and 200 A at 70 °C. For a panel running warm — say 55 °C ambient inside the enclosure — the usable continuous current drops to 238 A, not the nameplate 250 A. The thermal-magnetic trip unit has a minimum setting of 375 A and maximum of 2 500 A, covering a wide range of overload and short-circuit protection profiles. ## Auxiliaries and communication A communication function is built in, allowing integration with higher-level monitoring or control systems without an external module. ## Integration and footprint The 3-pole form factor matches typical three-phase feeder or distribution applications.","metaTitle":"Siemens 3VA2225-6KP32-0DL0 SENTRON MCCB, 250 A, 3-Pole","metaDescription":"Siemens 3VA2225-6KP32-0DL0 SENTRON molded case circuit breaker, 250 A continuous, 3-pole, 242 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","title":"3VA2225-6KP32-0DL0","Height":"181 mm","Maximum":"2 500 A","Minimum":"375 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"238 A","at 60 °C":"225 A","at 65 °C":"213 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","description":"circuit breaker 3VA2 IEC frame 250 breaking capacity class H Icu=85kA @ 415V 3-pole, line protection ETU850, LSI, In=250A overload protection Ir=100A...250A short-circuit protection Isd=0.6..10x In, Ii=1.5..10x In N conductor protection optionally with external current transformer nut keeper kit undervoltage release (UVR) 208-230V AC 50/60Hz 2 auxiliary switches HQ 1 trip alarm switch HQ 1 electrical alarm switch","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"50.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Of The Supplied Basic Switch":"3VA2225-6KP32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=36114&mlfb=3VA2225-6KP32-0DL0"},"ai":{"faq":[{"question":"Where can I buy 3VA2225-6KP32-0DL0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of 3VA2225-6KP32-0DL0 at different voltages?","answer":"The breaker delivers 242 kA at 240 V, 187 kA at both 415 V and 440 V, 121 kA at 500 V, and 4.5 kA at 690 V."},{"question":"Does 3VA2225-6KP32-0DL0 include an undervoltage release?","answer":"Yes, it is factory-fitted with an undervoltage release (UVR) that trips the breaker when control voltage drops below the dropout threshold."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6KP32-0DL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6KP32-0DL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}