{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6KP32-0JL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6KP32-0JL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6KP32-0JL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6KP32-0JL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-6KP32-0JL0, molded case circuit breaker, 3-pole, 250 A rated continuous current Iu, 242 kA interrupting capacity at 240 V, ETU850 electronic trip unit, line protection, shunt trip STL, 86 mm depth × 105 mm width × 181 mm height.","salesMarkdown":"At 415 V and 440 V it still holds 187 kA, and at 690 V it drops to 6 kA, so the voltage you're protecting determines the available fault current it can handle. Derate it as the ambient climbs: still 250 A at 50 °C, then 238 A at 55 °C, 225 A at 60 °C, 213 A at 65 °C, and 200 A at 70 °C. The ETU850 electronic trip unit gives you communication and measurement functions — voltage trigger and other measurement functions are built in. That means this breaker can talk to a BMS or PLC about what it's seeing, not just trip. The shunt trip (STL) auxiliary release lets you remotely open the breaker via a control signal, which is handy for emergency stops or sequenced shutdowns. That width matters in a multi-breaker lineup — three of these side by side eat 315 mm of DIN-rail or panel-mount space. The 86 mm depth includes the case body; make sure your gland plate or enclosure door clears it, especially if you're adding the auxiliary switch block or shunt trip wiring. That's a full complement for status feedback — breaker open/closed, trip event, and electrical alarm. The storage limit governs shipping and warehousing — it'll survive a cold warehouse or a hot truck, but the operating range is what matters in the panel.","metaTitle":"Siemens 3VA2225-6KP32-0JL0 SENTRON MCCB, 250 A, 242 kA","metaDescription":"Siemens 3VA2225-6KP32-0JL0 SENTRON MCCB, 250 A continuous, 242 kA at 240 V. Line protection, ETU850 release, 3-pole. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"6 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"238 A","at 60 °C":"225 A","at 65 °C":"213 A","at 70 °C":"200 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"Yes","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"48 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Rated continuous current Iu":"250 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2225-6KP32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU850","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"15","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"250 A","Adjustable response value current / li max.":"2 500 A","Adjustable response value current / li min.":"375 A","Adjustable response value current / lr min.":"100 A","Adjustable response value current / Isd max.":"2 500 A","Adjustable response value current / Isd min.":"150 A","Neutral conductors / upgradeable/retrofittable":"Yes","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=254542&mlfb=3VA2225-6KP32-0JL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6KP32-0JL0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2225-6KP32-0JL0?","answer":"We source and quote this breaker to order against an RFQ. Availability and current pricing are confirmed at quote time — submit a request and we'll run it through our distribution channels."},{"question":"What is the interrupting capacity of 3VA2225-6KP32-0JL0 at different voltages?","answer":"At 240 V it's 242 kA; at 415 V and 440 V it's 187 kA; at 500 V it's 121 kA; and at 690 V it drops to 6 kA. The voltage of your system determines the available fault current this breaker can safely interrupt."},{"question":"What are the physical dimensions of 3VA2225-6KP32-0JL0?","answer":"Width is 105 mm, height is 181 mm, and depth is 86 mm. That width is the critical fit dimension for multi-breaker lineups on DIN rail or panel mounting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6KP32-0JL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6KP32-0JL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}