{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-6KP32-0KL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-6KP32-0KL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-6KP32-0KL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6KP32-0KL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-6KP32-0KL0, molded case circuit breaker, 3-pole, 250 A continuous, 242 kA breaking capacity at 240 V, line protection design with communication function.","salesMarkdown":"The Siemens SENTRON 3VA2225-6KP32-0KL0 is a 3-pole molded case circuit breaker (MCCB) rated for 250 A continuous current at 40 °C, with a breaking capacity of 242 kA at 240 V. At 415 V and 440 V the rating holds at 187 kA, dropping to 121 kA at 500 V, and 4.5 kA at 690 V. The continuous current derates as ambient rises: still 250 A at 50 °C, then 238 A at 55 °C, 225 A at 60 °C, 213 A at 65 °C, and 200 A at 70 °C. If your panel runs hot, size the load accordingly — the 70 °C figure is the operating maximum per the datasheet. This is a line-protection design (not motor-protection), meaning it's intended for feeder circuits and distribution panels rather than individual motor overload protection. It includes a communication function, a trip indicator, and a voltage trigger. No undervoltage release is fitted, and no ground-fault monitoring is included — if you need those, you'd be looking at a different variant. Maximum power loss is 48 W. Dimensions are 105 mm wide, 181 mm high, 86 mm deep — the 105 mm width is the standard 3-pole MCCB footprint for this SENTRON frame size, so it fits existing panel cutouts and busbar arrangements without modification. ## Deployment context This MCCB mounts in a distribution panel or switchboard — it's a panel-mount device, not DIN-rail snap-on. The 105 mm width and 181 mm height fit standard SENTRON 3VA2225 frame cutouts. The shunt trip (STL) allows remote tripping for emergency-stop or supervisory control circuits. The communication function supports integration with higher-level monitoring systems, though the specific protocol is not detailed in this listing.","metaTitle":"Siemens 3VA2225-6KP32-0KL0 SENTRON MCCB, 250 A, 242 kA at 24","metaDescription":"Siemens SENTRON 3VA2225-6KP32-0KL0 molded case circuit breaker, 250 A continuous, 242 kA breaking at 240 V. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"2 500 A","Minimum":"375 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"238 A","at 60 °C":"225 A","at 65 °C":"213 A","at 70 °C":"200 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"48 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Of The Supplied Basic Switch":"3VA2225-6KP32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=491311&mlfb=3VA2225-6KP32-0KL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-6KP32-0KL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2225-6KP32-0KL0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is 3VA2225-6KP32-0KL0's listed depth (86 mm) on this component line?","answer":"The depth is 86 mm (3.39 in), with a width of 105 mm (4.13 in) and height of 181 mm (7.13 in)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-6KP32-0KL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-6KP32-0KL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}