{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-7HL32-0AG0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-7HL32-0AG0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-7HL32-0AG0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-7HL32-0AG0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-7HL32-0AG0, molded case circuit breaker, 3-pole, 250 A rated continuous current, line protection design, breaking capacity 330 kA at 240 V.","salesMarkdown":"It carries a maximum breaking capacity of 2,500 A and a minimum of 375 A, with voltage-dependent interrupting ratings that reach 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 4.5 kA at 690 V — so the same breaker body handles everything from low-voltage service entrances up to 690 V motor branch circuits, with the interrupting rating scaling to match the available fault current at each voltage level. Rated 250 A from 40 °C through 50 °C ambient; above that it derates linearly to 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C. That means in a sealed, uncooled enclosure hitting 60 °C — common in packed MCC lineups — you lose about 7 % of the continuous rating. The 86 mm depth, 105 mm width, and 181 mm height (3.39 × 4.13 × 7.13 in) fit standard SENTRON panel cutouts; the 3-pole block occupies the same footprint as other 250 A frames in the series, so a panel laid out for a 3VA2 can take this unit without re-drilling the gland plate.","metaTitle":"Siemens 3VA2225-7HL32-0AG0 SENTRON MCCB, 250 A, 3-Pole, Line","metaDescription":"Siemens SENTRON 3VA2225-7HL32-0AG0 molded case circuit breaker, 250 A rated, 3-pole, line protection. Breaking capacity 330 kA at 240 V. Active production. Available to order. Requ","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"2 500 A","Minimum":"375 A","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"241 A","at 60 °C":"232 A","at 65 °C":"222 A","at 70 °C":"213 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"48 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2225-7HL32-0AA0","Design Of The Auxiliary Switch":"1 auxiliary switch + 1 trip alarm switch HP","Design Of The Auxiliary Release":"Without auxiliary release","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB11","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=152943&mlfb=3VA2225-7HL32-0AG0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-7HL32-0AG0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2225-7HL32-0AG0 at 415 V?","answer":"242 kA at 415 V, which is the same rating it carries at 440 V; it drops to 187 kA at 500 V and 4.5 kA at 690 V."},{"question":"How does the 3VA2225-7HL32-0AG0 compare to the 5SQ2370-2YA05?","answer":"The 5SQ2370-2YA05 is a physically different frame — the 3VA2225 uses the SENTRON 3VA2 platform with 86 × 105 × 181 mm dimensions, while the 5SQ series is an older Siemens MCCB line. They are not drop-in interchangeable without verifying the cutout and bus-bar spacing; the 3VA2 is the current-production replacement architecture."},{"question":"Where can I buy 3VA2225-7HL32-0AG0 and get current pricing?","answer":"This part is sourced and quoted to order through independent distribution against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-7HL32-0AG0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-7HL32-0AG0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}