{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-7HL32-0HH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-7HL32-0HH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-7HL32-0HH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-7HL32-0HH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-7HL32-0HH0, molded case circuit breaker, 3-pole, 250 A, 330 kA at 240 V, line protection, shunt trip, 2 aux + 1 trip alarm.","salesMarkdown":"Its breaking capacity hits 330 kA at 240 VAC — that's the figure to check against your available fault current; at 415 V it still holds 242 kA, and at 690 V it drops to 4.5 kA, so this is a 240–500 V breaker, not a 690 V main. The 3VA2225 frame measures 105 mm wide, 181 mm tall, 86 mm deep — standard for a 250 A SENTRON MCCB. The shunt trip (STL) requires a separate control voltage to trip; verify your control transformer and wiring match the STL coil rating. No communication function on this variant — if you need Modbus or PROFIBUS, look at the 3VA2 with communication module option.","metaTitle":"Siemens 3VA2225-7HL32-0HH0 SENTRON MCCB, 250 A, 3-Pole, 330","metaDescription":"Siemens SENTRON 3VA2225-7HL32-0HH0 molded case circuit breaker, 250 A continuous, 3-pole, 330 kA breaking at 240 VAC. Current lifecycle. Sourced to order. Request RFQ for pricing a","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"2 500 A","Minimum":"375 A","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"241 A","at 60 °C":"232 A","at 65 °C":"222 A","at 70 °C":"213 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"48 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2225-7HL32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=367336&mlfb=3VA2225-7HL32-0HH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-7HL32-0HH0/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of 3VA2225-7HL32-0HH0?","answer":"The depth is 86 mm (3.39 in)."},{"question":"What is the width of 3VA2225-7HL32-0HH0?","answer":"The width is 105 mm (4.13 in)."},{"question":"Does 3VA2225-7HL32-0HH0 include a shunt trip and auxiliary switches?","answer":"Yes, it includes a shunt trip (STL) and two auxiliary switches plus one trip alarm switch (HQ)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-7HL32-0HH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-7HL32-0HH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}