{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-7HL32-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-7HL32-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-7HL32-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-7HL32-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-7HL32-0JH0, molded case circuit breaker, 3-pole, 250 A continuous, line protection, 330 kA breaking capacity at 240 V AC.","salesMarkdown":"Its interrupting capacity reaches 330 kA at 240 V AC, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 4.5 kA at 690 V — figures that define the available fault current it can safely clear without upstream cascading. The 250 A rating holds flat from 40 °C through 50 °C ambient, then derates to 241 A at 55 °C, 232 A at 60 °C, 222 A at 65 °C, and 213 A at 70 °C. For a panel OEM or MRO planner slotting this into an existing enclosure, the dimensions are 105 mm wide, 181 mm high, and 86 mm deep — a 3-pole footprint that drops into a standard SENTRON 3VA mounting base without rewiring from the 3VA2116-5JP32-0AE0 or other 3VA frame siblings, provided the busbar and lug kit match the 250 A continuous rating.","metaTitle":"Siemens 3VA2225-7HL32-0JH0 SENTRON MCCB, 250 A, 3-Pole, 330","metaDescription":"Siemens 3VA2225-7HL32-0JH0 SENTRON molded case circuit breaker, 250 A continuous, 3-pole, line protection, 330 kA SCCR at 240 V. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","Maximum":"2 500 A","Minimum":"375 A","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"4.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"241 A","at 60 °C":"232 A","at 65 °C":"222 A","at 70 °C":"213 A","Depth [In]":"3.39 in","Width [In]":"4.13 in","Height [In]":"7.13 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"48 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2225-7HL32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"250 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"25 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=80031&mlfb=3VA2225-7HL32-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-7HL32-0JH0/alternatives.json"},"ai":{"faq":[{"question":"Will 3VA2225-7HL32-0JH0 drop into a panel specified around 3VA2116-5JP32-0AE0 without rewiring?","answer":"Yes — both are 3-pole SENTRON 3VA frame MCCBs sharing the same 105 mm width, 181 mm height, and 86 mm depth, so the mechanical footprint and mounting base are identical. The busbar and lug kit must be rated for 250 A continuous on this variant versus the lower rating of the 3VA2116-5JP32-0AE0."},{"question":"What auxiliary switches and releases are fitted?","answer":"This variant includes 2 auxiliary switches plus 1 trip alarm switch (HQ design) and a shunt trip release (STL) for remote opening. There is no undervoltage release and no ground-fault monitoring module."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-7HL32-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-7HL32-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}