{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-7HN32-0LE0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-7HN32-0LE0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-7HN32-0LE0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-7HN32-0LE0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 IEC frame 250, breaking capacity class C, Icu=110kA @ 415V, 3-pole, line protection ETU350, LSI, In=250A, overload protection Ir=100A...250A, short-circuit protection Isd=1.5...10 x Ir, Ii=10 x In, nut keeper kit, universal release 24 V DC accessory for 3VA1 and 3VA20 up to 4 auxiliary.","salesMarkdown":"The Siemens 3VA2225-7HN32-0LE0 is a 3-pole IEC frame 250 molded-case circuit breaker with a breaking capacity class C rating of 110 kA at 415 V. Overload protection (Ir) is adjustable from 100 A to 250 A; short-time pickup (Isd) ranges from 1.5 to 10 times Ir, and instantaneous pickup (Ii) is fixed at 10 times In. The listing also includes a nut keeper kit and a universal release accessory for 24 V DC, compatible with 3VA1 and 3VA20 frames up to four auxiliary contacts.","metaTitle":"Siemens 3VA2225-7HN32-0LE0 Circuit Breaker, 250A, 110kA @ 41","metaDescription":"Siemens 3VA2225-7HN32-0LE0 IEC frame 250 circuit breaker, 110kA breaking capacity at 415V, ETU350 LSI, 250A. Current lifecycle stage. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1342937&mlfb=3VA2225-7HN32-0LE0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-7HN32-0LE0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2225-7HN32-0LE0?","answer":"The breaking capacity is 110 kA at 415 V (Icu), classification class C per IEC."},{"question":"What trip unit and protection functions does this breaker have?","answer":"It uses an ETU350 electronic trip unit with LSI protection: long-time (Ir adjustable 100–250 A), short-time (Isd adjustable 1.5–10 x Ir), and instantaneous (Ii fixed at 10 x In)."},{"question":"Where can I buy 3VA2225-7HN32-0LE0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-7HN32-0LE0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-7HN32-0LE0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}