{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2225-7KP32-0JL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2225-7KP32-0JL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2225-7KP32-0JL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2225-7KP32-0JL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2225-7KP32-0JL0, molded case circuit breaker, 250 A, 3-pole, line protection, ETU850 electronic trip unit, 330 kA at 240 V.","salesMarkdown":"## What this MCCB delivers — 250 A continuous, 330 kA interrupting at 240 V It carries a 3-pole line protection configuration with an ETU850 electronic overcurrent release, giving you adjustable trip curves and communication capability for selective coordination studies. Breaking capacity is 330 kA at 240 V, dropping to 242 kA at 415 V and 440 V, 187 kA at 500 V, and 6.3 kA at 690 V — numbers that place this breaker in the high-interrupting category for large service entrances or heavy industrial feeders. ## Auxiliary contacts and trip options built in A voltage trigger is present; undervoltage release is not. The breaker also has a mechanical trip indicator and latching endurance rated at 20,000 operations. The 105 mm width matches the standard 3-pole MCCB slot in most switchgear lineups. The ETU850 release is field-configurable via the front face — no need to pull the breaker for trip-curve changes.","metaTitle":"Siemens 3VA2225-7KP32-0JL0 SENTRON MCCB, 250 A, 3-Pole, Line","metaDescription":"Siemens 3VA2225-7KP32-0JL0 SENTRON molded case circuit breaker, 250 A rated continuous current, 3-pole, line protection, ETU850 release, 330 kA at 240 V. Active production, sourced","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"86 mm","Width":"105 mm","Height":"181 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"6.3 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"238 A","at 60 °C":"225 A","at 65 °C":"213 A","at 70 °C":"200 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"20 000","Undervoltage Release":"No","Communication Function":"Yes","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"48 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Rated continuous current Iu":"250 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2225-7KP32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU850","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"15","Adjustable response value time / tr min.":"0.5","Adjustable response value time / tsd max.":"0.5 s","Adjustable response value time / tsd min.":"0.05 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"250 A","Adjustable response value current / li max.":"2 500 A","Adjustable response value current / li min.":"375 A","Adjustable response value current / lr min.":"100 A","Adjustable response value current / Isd max.":"2 500 A","Adjustable response value current / Isd min.":"150 A","Neutral conductors / upgradeable/retrofittable":"Yes","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching capacity class of the circuit breaker":"C","Max. rated operational current of the frame size":"250 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"25 x 8.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"13 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a7c0d29262bf1366bc093fc9653b1e6.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=483705&mlfb=3VA2225-7KP32-0JL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2225-7KP32-0JL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2225-7KP32-0JL0 and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a quote request for current pricing and availability — no minimum quantity barrier."},{"question":"Will 3VA2225-7KP32-0JL0 drop into a panel specified around 3VA2225-5JQ32-0AK0 without rewiring?","answer":"Both breakers share the same 3-pole SENTRON frame and 105 mm width, so the mechanical fit and busbar connection are identical. The key difference is the trip unit: the -7KP32-0JL0 uses an ETU850 electronic release with communication, while the -5JQ32-0AK0 uses a different release. Verify that the control wiring for the shunt trip and auxiliary contacts matches your panel schematic — the terminal assignments are the same, but the ETU850 may require an additional communication cable if you use that feature."},{"question":"What compliance documentation does Siemens provide for 3VA2225-7KP32-0JL0?","answer":"Siemens provides RoHS and REACH declarations, plus UL, CSA, and IEC 60947-2 certifications for the SENTRON series. The specific declaration of conformity and test reports are available on request with the order."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2225-7KP32-0JL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2225-7KP32-0JL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}