{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-0MS32-0KD0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-0MS32-0KD0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-0MS32-0KD0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-0MS32-0KD0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 IEC frame 400 circuit breaker, breaking capacity class E, Icu=200 kA @ 415 V, 3-pole, motor starter protection ETU310M, In=250 A, shunt trip left 208-277 V AC / 220-250 V DC, 3 auxiliary switch changeover H.","salesMarkdown":"## Breaking capacity and trip unit The Siemens 3VA2325-0MS32-0KD0 is a 3-pole IEC frame 400 circuit breaker rated for 250 A continuous current, with a breaking capacity Icu of 200 kA at 415 V AC — that is class E in the 3VA2 line, meaning it handles very high fault currents typical of large transformer-fed distribution or motor control centers without needing an upstream current-limiting device. The ETU310M trip unit is a microprocessor-based release with adjustable short-circuit protection Ii from 3 to 15 times In, so you can tune the magnetic pickup to match motor inrush or feeder coordination curves without swapping the breaker. ## Accessories and control wiring Includes three auxiliary switch changeover contacts (form C) for remote status indication or interlocking; the busbar connection pattern matches the 3VA2 frame footprint, so it lands directly on standard Siemens panelboard or switchboard bus stacks.","metaTitle":"Siemens 3VA2325-0MS32-0KD0 3VA2 IEC Frame 400, 200 kA @ 415","metaDescription":"Siemens 3VA2325-0MS32-0KD0 circuit breaker, 3VA2 IEC frame 400, 200 kA breaking capacity at 415 V, 3-pole, ETU310M trip unit, 250 A, with shunt trip and 3 auxiliary switches. Lifec","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"title":"3VA2325-0MS32-0KD0","description":"circuit breaker 3VA2 IEC frame 400 breaking capacity class E Icu=200 kA @ 415 V 3-pole motor starter protection ETU310M, I, In=250A short circuit protection Ii=3...15 x In busbar connection SHUNT TRIP LEFT 208-277 V AC 50/60 HZ 220-250 V DC ACCESSORY 3 AUXILIARY SWITCH CHANGEOVER H","lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1532103&mlfb=3VA2325-0MS32-0KD0"},"ai":{"faq":[{"question":"What is 3VA2325-0MS32-0KD0's breaking capacity?","answer":"The rated ultimate breaking capacity Icu is 200 kA at 415 V AC, which is class E on the 3VA2 IEC frame 400."},{"question":"What trip unit and adjustments does this breaker have?","answer":"It uses the ETU310M microprocessor-based trip unit with adjustable short-circuit protection Ii from 3 to 15 times the 250 A rated current (In)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-0MS32-0KD0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-0MS32-0KD0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}