{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-5HL32-0AF0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-5HL32-0AF0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-5HL32-0AF0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-5HL32-0AF0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2325-5HL32-0AF0, molded case circuit breaker, 3-pole, 250 A continuous, line protection, 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 500 V.","salesMarkdown":"It carries a continuous current rating of 250 A across the full ambient range from 40 °C to 70 °C, meaning no derating is needed as the panel warms up; the breaker delivers its full 250 A at 70 °C ambient. Breaking capacity is the key selection number for fault duty. At 240 V it interrupts 187 kA; at 415 V and 440 V it holds 121 kA; at 500 V it drops to 75.6 kA; at 690 V it is still rated at 7.5 kA. The 3-pole design (3 poles) and the trip indicator (trip indicator present) let the operator see at a glance whether the breaker has tripped on a fault — no need to probe with a meter on a darkened panel. Dimensions are 248 mm high, 138 mm wide, 110 mm deep — a standard SENTRON 3VA frame size that fits the usual DIN-rail or mounting-plate footprint for 250 A MCCBs. The auxiliary switch configuration (1 auxiliary switch + 1 trip alarm switch HQ) provides one N.O./N.C. set for status feedback and a separate alarm contact that closes only on a trip event, not on manual switching. The 138 mm width occupies three module spaces on a DIN rail. Power loss is 37.5 W maximum at rated load. In a sealed, non-ventilated enclosure, that heat must be factored into the thermal budget — at 250 A continuous, the breaker itself runs warm, so keep adjacent wiring and components clear of the top vent slots.","metaTitle":"Siemens 3VA2325-5HL32-0AF0 SENTRON MCCB, 250 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2325-5HL32-0AF0 molded case circuit breaker, 250 A continuous, 3-pole, 187 kA breaking at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"3 000 A","Minimum":"375 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"7.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"250 A","at 60 °C":"250 A","at 65 °C":"250 A","at 70 °C":"250 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"37.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2325-5HL32-0AA0","Design Of The Auxiliary Switch":"1 auxiliary switch + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"Without auxiliary release","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=476300&mlfb=3VA2325-5HL32-0AF0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-5HL32-0AF0/alternatives.json"},"ai":{"faq":[{"question":"Does 3VA2325-5HL32-0AF0 have a trip indicator?","answer":"Yes, it includes a trip indicator that shows visually whether the breaker has tripped on a fault."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-5HL32-0AF0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-5HL32-0AF0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}