{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-5HL32-0AG0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-5HL32-0AG0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-5HL32-0AG0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-5HL32-0AG0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2325-5HL32-0AG0, molded case circuit breaker, 3-pole, 250 A continuous rating, line protection design, 187 kA breaking capacity at 240 V.","salesMarkdown":"The 3VA2 frame carries a 3 000 A maximum interrupt rating; this specific unit is set at a 375 A minimum, 3 000 A maximum, so the trip unit is adjustable across that band. ## Breaking capacity — the real fit number Breaking capacity is where the 3VA2325-5HL32-0AG0 earns its place in a panel schedule. At 240 V it interrupts 187 kA — that's utility-transformer-level fault current, typical for a main service entrance or a large sub-distribution board. Footprint is 138 mm wide by 248 mm tall by 110 mm deep — a 3-pole MCCB in a standard SENTRON 3VA2 frame. ## Auxiliary switch and trip indication The trip indicator is present, so a visual flag shows when the breaker has tripped on fault — useful for a maintenance tech walking a lineup. No communication function, no voltage trigger, no auxiliary release. This is a standalone breaker, not a smart breaker with IO-Link or PROFINET. ## Thermal limits and power loss Maximum power loss is 37.5 W at rated current — that heat has to be managed inside the enclosure, so factor it into the panel cooling calculation if the breaker is in a sealed box with other heat sources.","metaTitle":"Siemens 3VA2325-5HL32-0AG0 SENTRON MCCB, 250 A, 3-Pole, Line","metaDescription":"Siemens SENTRON 3VA2325-5HL32-0AG0 molded case circuit breaker, 250 A continuous, 3-pole, line protection. Breaking capacity 187 kA at 240 V. Active production. Quoted to order aga","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"3 000 A","Minimum":"375 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"7.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"250 A","at 60 °C":"250 A","at 65 °C":"250 A","at 70 °C":"250 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"37.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2325-5HL32-0AA0","Design Of The Auxiliary Switch":"1 auxiliary switch + 1 trip alarm switch HP","Design Of The Auxiliary Release":"Without auxiliary release","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB11","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=449939&mlfb=3VA2325-5HL32-0AG0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-5HL32-0AG0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2325-5HL32-0AG0 at 240 V?","answer":"187 kA at 240 V, which covers utility-transformer-level fault current for main service entrance applications."},{"question":"Where can I buy 3VA2325-5HL32-0AG0 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-5HL32-0AG0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-5HL32-0AG0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}