{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-5HL32-0CA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-5HL32-0CA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-5HL32-0CA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-5HL32-0CA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2325-5HL32-0CA0, molded case circuit breaker, 3-pole, 250 A continuous, line protection, with undervoltage release, 187 kA at 240 V.","salesMarkdown":"The Siemens SENTRON 3VA2325-5HL32-0CA0 is a 3-pole molded case circuit breaker rated for 250 A continuous current across the full 40 °C to 70 °C ambient range — no derating curve to chase. The interrupting ratings climb to 187 kA at 240 VAC and hold at 121 kA through 440 VAC, then step down to 75.6 kA at 500 VAC and 7.5 kA at 690 VAC. That's enough SCCR headroom for most industrial service-entrance panels on 480 V or 400 V systems. Max power loss is 40 W, which matters for enclosure thermal budgeting when you're stacking several breakers in a row. ## What the undervoltage release means in practice It's wired separately from the main power path, so you need a control voltage source (typically 24 VDC or 120 VAC, depending on the release coil ordered). No auxiliary switch is fitted on this variant, so if you need remote status feedback, plan for an add-on auxiliary contact block.","metaTitle":"Siemens 3VA2325-5HL32-0CA0 SENTRON MCCB, 250 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2325-5HL32-0CA0 molded case circuit breaker, 250 A continuous, 3-pole, 187 kA at 240 VAC. Line protection with undervoltage release. Current lifecycle. Sourced t","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"3 000 A","Minimum":"375 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"7.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"250 A","at 60 °C":"250 A","at 65 °C":"250 A","at 70 °C":"250 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"40 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2325-5HL32-0AA0","Design Of The Auxiliary Switch":"Without","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=258306&mlfb=3VA2325-5HL32-0CA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-5HL32-0CA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2325-5HL32-0CA0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What compliance documentation does Siemens provide for this MCCB?","answer":"Siemens SENTRON 3VA breakers are typically supplied with IEC 60947-2 certification and CE marking. RoHS and REACH declarations are available through Siemens' documentation portal. Specific UL listing should be confirmed per variant — this order code's evidence does not list a UL file number."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-5HL32-0CA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-5HL32-0CA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}