{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-5HL32-0KF0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-5HL32-0KF0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-5HL32-0KF0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-5HL32-0KF0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 series, IEC frame 400, breaking capacity class M, Icu=55kA @ 415V, 3-pole, line protection ETU320, LI, In=250A, overload protection Ir=100A...250A, short-circuit protection Ii=1.5...12 x In, nut keeper kit, shunt trip (STL) 220-250V DC / 208-277V AC, 1 auxiliary switch HQ, 1 trip alarm switch HQ.","salesMarkdown":"## Panel-builder commissioning notes The 3VA2325-5HL32-0KF0 is a current-production IEC frame 400 molded-case circuit breaker from the Siemens 3VA2 line, rated for 250 A continuous with an Icu of 55 kA at 415 V AC — that's the maximum fault current it can safely interrupt without damage, sized for high-fault industrial distribution panels where a standard 25 kA breaker would weld closed on a bolted fault. The ETU320 electronic trip unit provides LI (long-time and instantaneous) protection: overload pickup adjustable from 100 A to 250 A, and short-circuit pickup from 1.5× to 12× In, so you can coordinate selectively with downstream feeders without nuisance tripping on motor inrush. ## DIN-rail integration and fill factor The 3-pole footprint occupies three module widths — plan gland-plate knockouts accordingly when laying out a multi-breaker panel. ## Shunt trip and auxiliary wiring The factory-fitted shunt trip (STL) operates on 220–250 V DC or 208–277 V AC, letting you remote-trip the breaker from an E-stop or fire-alarm relay without a separate interposing contactor.","metaTitle":"Siemens 3VA2325-5HL32-0KF0 Circuit Breaker, 250A, 55kA @ 415","metaDescription":"Siemens 3VA2325-5HL32-0KF0 IEC frame 400 breaker, 55kA Icu @ 415V, ETU320 LI trip, 250A, shunt trip. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=765450&mlfb=3VA2325-5HL32-0KF0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-5HL32-0KF0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this breaker?","answer":"The 3VA2325-5HL32-0KF0 has an Icu of 55 kA at 415 V AC, which is the maximum fault current it can safely interrupt without damage."},{"question":"What does the ETU320 trip unit protect against?","answer":"The ETU320 provides LI protection: long-time (overload) adjustable from 100 A to 250 A, and instantaneous (short-circuit) adjustable from 1.5× to 12× In."},{"question":"How do I get pricing and availability for the 3VA2325-5HL32-0KF0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability confirmation."},{"question":"Does this breaker include a shunt trip and auxiliary contacts?","answer":"Yes, it comes with a shunt trip (STL) rated 220–250 V DC / 208–277 V AC, one HQ auxiliary switch, and one trip alarm switch."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-5HL32-0KF0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-5HL32-0KF0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}