{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-5HL32-0KH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-5HL32-0KH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-5HL32-0KH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-5HL32-0KH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2325-5HL32-0KH0, molded case circuit breaker, 3-pole, 250 A rated continuous current, 187 kA breaking capacity at 240 V AC, line protection design.","salesMarkdown":"The Siemens SENTRON 3VA2325-5HL32-0KH0 is a 3-pole molded case circuit breaker rated for 250 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling, which simplifies panel thermal budgeting. Its interrupting capacity hits 187 kA at 240 V AC, 121 kA at 415 V, and 75.6 kA at 500 V; at 690 V it still holds 7.5 kA. The shunt trip and auxiliary switch wiring exits through the front face, so leave clearance for the cable bend radius. Maximum power dissipation is 37.5 W at full load — account for that heat in the enclosure ventilation, especially if multiple breakers are ganged.","metaTitle":"Siemens 3VA2325-5HL32-0KH0 SENTRON MCCB, 250 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2325-5HL32-0KH0 molded case circuit breaker, 250 A rated, 3-pole, 187 kA breaking at 240 V. Active production. Sourced to order. RFQ for availability.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"3 000 A","Minimum":"375 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"7.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"250 A","at 60 °C":"250 A","at 65 °C":"250 A","at 70 °C":"250 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"37.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2325-5HL32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=54499&mlfb=3VA2325-5HL32-0KH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-5HL32-0KH0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2325-5HL32-0KH0 at 240 V?","answer":"The interrupting rating is 187 kA at 240 V AC, which is the highest value listed for this breaker across all voltage levels."},{"question":"Does 3VA2325-5HL32-0KH0 include auxiliary contacts?","answer":"Yes, it comes with 2 auxiliary switches and 1 trip alarm switch (HQ design) for status feedback."},{"question":"Where can I buy 3VA2325-5HL32-0KH0 and what is the lead time?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here."},{"question":"What is the rated continuous current of 3VA2325-5HL32-0KH0?","answer":"The rated continuous current is 250 A, and it holds that rating from 40 °C up to 70 °C ambient without derating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-5HL32-0KH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-5HL32-0KH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}