{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-5HN32-0BL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-5HN32-0BL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-5HN32-0BL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-5HN32-0BL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2325-5HN32-0BL0, molded case circuit breaker, 3-pole, 250 A, ETU350 electronic trip unit, line protection, 187 kA at 240 V.","salesMarkdown":"Breaking capacity is 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V — so the same breaker handles high-fault commercial mains and lower-fault industrial distribution without swapping frames. Current derating is published per ambient temperature: 250 A up to 50 °C, then 240 A at 55 °C, 235 A at 60 °C, 230 A at 65 °C, and 225 A at 70 °C. An undervoltage release (UVR) is integrated as the auxiliary release design. No communication function or phase-failure detection is built in — this is a standalone line-protection breaker, not a power-monitoring device. Dimensions: 138 mm wide, 248 mm high, 110 mm deep. The 138 mm width is the three-pole footprint — check your existing busbar or mounting plate spacing if replacing a different MCCB family. The 110 mm depth includes the rotary handle; clearance behind the panel for the arc chamber must be maintained per the manufacturer's installation instructions.","metaTitle":"Siemens 3VA2325-5HN32-0BL0 SENTRON MCCB, 250 A, 3-Pole, ETU3","metaDescription":"Siemens SENTRON 3VA2325-5HN32-0BL0 molded case circuit breaker, 250 A rated continuous current, 3-pole, ETU350 electronic trip, 187 kA at 240 V. Current production. Quoted to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"240 A","at 60 °C":"235 A","at 65 °C":"230 A","at 70 °C":"225 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"40 W","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"250 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2325-5HN32-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB11","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"250 A","Adjustable response value current / li max.":"3 000 A","Adjustable response value current / li min.":"3 000 A","Adjustable response value current / lr min.":"100 A","Adjustable response value current / Isd max.":"0 A","Adjustable response value current / Isd min.":"0 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"4","Protective function of the overcurrent release":"LSI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"400 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"35 x 10","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=506658&mlfb=3VA2325-5HN32-0BL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-5HN32-0BL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2325-5HN32-0BL0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of 3VA2325-5HN32-0BL0 at 415 V?","answer":"At 415 V the breaking capacity is 121 kA, matching the rating at 440 V. At 500 V it drops to 75.6 kA, and at 690 V to 17 kA."},{"question":"What trip unit does this MCCB use?","answer":"It uses the ETU350 electronic trip unit, which supports adjustable long-time, short-time, instantaneous, and ground-fault protection for selective coordination."},{"question":"Does 3VA2325-5HN32-0BL0 include an undervoltage release?","answer":"Yes, an undervoltage release (UVR) is integrated as the auxiliary release design. The auxiliary contact block provides 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ version)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-5HN32-0BL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-5HN32-0BL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}