{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-5HN32-0DL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-5HN32-0DL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-5HN32-0DL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-5HN32-0DL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2325-5HN32-0DL0, molded case circuit breaker, 250 A, 3-pole, line protection, 187 kA at 240 V, undervoltage release, 2 aux + 1 trip alarm + 1 electrical alarm switches.","salesMarkdown":"## Siemens SENTRON 3VA2325-5HN32-0DL0 — 250 A MCCB with Undervoltage Release Breaking capacity runs 187 kA at 240 V, 121 kA at 415 V, and 75.6 kA at 500 V, tapering to 7.5 kA at 690 V. That kind of headroom means it handles high-fault utility feeds or large transformer secondaries without upstream fuses. That is unusual for an MCCB this size; most lose 10–15 % by 60 °C. The 3 000 A frame means the internal trip mechanism is built for high short-circuit energy, so the breaker stays selective with downstream 100–200 A devices. At 690 V the interrupting rating drops to 7.5 kA, which still covers most 690 V motor circuits with typical transformer impedances. The auxiliary switch deck (2 aux + 1 trip alarm + 1 electrical alarm) gives you enough dry contacts for remote status, PLC inputs, and a separate trip-indication circuit without adding a side-mount block.","metaTitle":"Siemens 3VA2325-5HN32-0DL0 SENTRON MCCB, 250 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2325-5HN32-0DL0 molded case circuit breaker, 250 A continuous, 3-pole, 187 kA breaking capacity at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"3 000 A","Minimum":"3 000 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"7.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"250 A","at 60 °C":"250 A","at 65 °C":"250 A","at 70 °C":"250 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"40 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2325-5HN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=259668&mlfb=3VA2325-5HN32-0DL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-5HN32-0DL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2325-5HN32-0DL0 and how do I get a price?","answer":"This part is sourced to order against an RFQ through our independent distribution. Submit a quote request; availability and current pricing are confirmed at quote time."},{"question":"What is 3VA2325-5HN32-0DL0's breaking capacity at 240 V?","answer":"187 kA at 240 V, with 121 kA at 415 V and 75.6 kA at 500 V."},{"question":"Does this MCCB include an undervoltage release?","answer":"Yes, it is equipped with an undervoltage release (UVR) as the auxiliary release, plus two auxiliary switches, one trip alarm switch, and one electrical alarm switch."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-5HN32-0DL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-5HN32-0DL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}