{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-5HN32-0JA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-5HN32-0JA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-5HN32-0JA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-5HN32-0JA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2, Molded Case Circuit Breaker, 3-pole, Line protection, 250 A, 187 kA at 240 V, ETU350 release, Shunt trip (STL).","salesMarkdown":"Breaking capacity is the key fit question for a main breaker: this one delivers 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 17 kA at 690 V. At 690 V the 17 kA rating is lower, but still adequate for most 690 V motor control center applications where the transformer impedance limits fault current. Thermal derating is published: 250 A continuous from 40 °C through 50 °C, then 240 A at 55 °C, 235 A at 60 °C, 230 A at 65 °C, and 225 A at 70 °C. Maximum power loss is 37.5 W, which feeds into the enclosure heat budget. The 3VA2325-5HN32-0JA0 measures 138 mm wide, 248 mm tall, and 110 mm deep. ## What it does not include This version ships without auxiliary contacts, without a trip indicator, without an undervoltage release, without ground-fault monitoring, without communication, and without phase-failure detection. If your application requires any of those — say, a remote trip signal to a PLC or ground-fault protection on a solidly-grounded system — you need a different 3VA2 variant or an accessory kit. The shunt trip (STL) is the only auxiliary release fitted.","metaTitle":"Siemens 3VA2325-5HN32-0JA0 SENTRON MCCB, 250 A, 187 kA at 24","metaDescription":"Siemens SENTRON 3VA2325-5HN32-0JA0 molded case circuit breaker, 250 A rated, 3-pole, line protection with ETU350 release and shunt trip. Breaking capacity 187 kA at 240 V. Current","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"17 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"240 A","at 60 °C":"235 A","at 65 °C":"230 A","at 70 °C":"225 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"37.5 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"250 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2325-5HN32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"250 A","Adjustable response value current / li max.":"3 000 A","Adjustable response value current / li min.":"3 000 A","Adjustable response value current / lr min.":"100 A","Adjustable response value current / Isd max.":"0 A","Adjustable response value current / Isd min.":"0 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"M","Max. rated operational current of the frame size":"400 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"35 x 10","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=65858&mlfb=3VA2325-5HN32-0JA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-5HN32-0JA0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-5HN32-0JA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-5HN32-0JA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}