{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-5KP32-0KE0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-5KP32-0KE0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-5KP32-0KE0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-5KP32-0KE0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, molded case circuit breaker, 3VA2325-5KP32-0KE0, 250 A, 3-pole, ETU850 electronic trip unit, 187 kA at 240 V.","salesMarkdown":"The 3-pole unit carries an ETU850 electronic trip unit with adjustable long-time (Ig) and instantaneous (Ii) pickup, covering 0.5 s minimum response and 375–3000 A short-circuit range. Breaking capacity reaches 187 kA at 240 V, 121 kA at 415 V, and 55 kA at 440 V, so it handles high-fault utility feeds without cascading upstream. Dimensions: 138 mm wide, 248 mm high, 110 mm deep. The 138 mm width (5.4 in) is the critical dimension for multi-pole grouping on a DIN-rail or backplate — verify your enclosure fill factor against this footprint. Depth of 110 mm leaves room behind the gland plate for wiring and the optional motor drive. The ETU850 trip unit is field-adjustable for Ig (0.5 s minimum) and Ii (375–3000 A). No ground-fault monitoring is integrated — specify an external module if GF protection is required. Neutral conductor protection is not included but is upgradeable/retrofittable. The unit is designed for line protection (cable/feeder), not motor protection; pair it with a separate overload relay for motor circuits.","metaTitle":"Siemens 3VA2325-5KP32-0KE0 SENTRON MCCB, 250 A, 3-Pole, ETU8","metaDescription":"Siemens 3VA2325-5KP32-0KE0 SENTRON molded case circuit breaker, 250 A rated, 3-pole, ETU850 trip unit, 187 kA at 240 V. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"55 kA","at 500 V":"36 kA","at 690 V":"7.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"250 A","at 60 °C":"250 A","at 65 °C":"250 A","at 70 °C":"250 A","Width [In]":"5.4 in","Height [In]":"9.8 in","Number Of Poles":"3","Product version":"Line protection","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"37.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Ground-Fault Monitoring Version":"Without","Tension assignée d'isolement Ui":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"Without","reference code / acc. to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / lg min.":"0.5 s","Adjustable response value current / li max.":"3 000 A","Adjustable response value current / li min.":"375 A","Neutral conductors / upgradeable/retrofittable":"Yes","Protection Function Of The Overcurrent Release":"LSI","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Switching Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"Lug terminal","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"35 x 10","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=587807&mlfb=3VA2325-5KP32-0KE0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-5KP32-0KE0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2325-5KP32-0KE0 at 240 V?","answer":"187 kA at 240 V, with 121 kA at 415 V and 55 kA at 440 V — sufficient for high-fault utility feeds."},{"question":"Where can I buy 3VA2325-5KP32-0KE0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"Does 3VA2325-5KP32-0KE0 include ground-fault protection?","answer":"No, this version is without ground-fault monitoring. An external module is required for GF protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-5KP32-0KE0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-5KP32-0KE0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}