{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-5MN32-0CH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-5MN32-0CH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-5MN32-0CH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-5MN32-0CH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2, molded case circuit breaker, 3VA2325-5MN32-0CH0, 250 A, 3-pole, motor protection design, interrupting capacity 187 kA at 240 V.","salesMarkdown":"Interrupting capacity is 187 kA at 240 V, tapering to 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V. That 187 kA at 240 V handles high-fault utility feeds or transformer secondaries; the 7.5 kA at 690 V still clears a fault on a 690 V drive bus. Trip time is adjustable between 4 s and 17 s, matching motor start profiles without nuisance trips. Mounts in a standard panel enclosure — the 138 mm width and 248 mm height fit a typical MCCB cutout. The undervoltage release (UVR) is built in, so no separate coil or monitoring relay is needed for undervoltage protection. Phase failure detection is integrated; no external phase-loss module required. The trip indicator gives a local visual of the breaker state without opening the door.","metaTitle":"Siemens 3VA2325-5MN32-0CH0 SENTRON MCCB, 250 A, 3-Pole, Moto","metaDescription":"Siemens 3VA2325-5MN32-0CH0 SENTRON molded case circuit breaker, 250 A rated at 40-70 °C, 3-pole, motor protection with phase failure detection. Interrupting capacity 187 kA at 240","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"17 s","Minimum":"4 s","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"7.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"250 A","at 60 °C":"250 A","at 65 °C":"250 A","at 70 °C":"250 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"40 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2325-5MN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"55 000 W","operating power / at AC-3 / at 400 V":"110 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570000&mlfb=3VA2325-5MN32-0CH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-5MN32-0CH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2325-5MN32-0CH0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the interrupting capacity of 3VA2325-5MN32-0CH0 at different voltages?","answer":"At 240 V it interrupts 187 kA; at 415 V and 440 V it interrupts 121 kA; at 500 V it interrupts 75.6 kA; at 690 V it interrupts 7.5 kA. These ratings cover utility feeds, motor branch circuits, and 690 V drive applications."},{"question":"Does 3VA2325-5MN32-0CH0 include phase failure detection?","answer":"Yes, phase failure detection is built in. It also includes an undervoltage release (UVR) and a trip indicator."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-5MN32-0CH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-5MN32-0CH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}