{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-5MN32-0DL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-5MN32-0DL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-5MN32-0DL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-5MN32-0DL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2325-5MN32-0DL0, molded case circuit breaker, 3-pole, 250 A, motor protection design, with undervoltage release and auxiliary switches.","salesMarkdown":"It is a 3-pole unit rated at 250 A continuously at 40 °C, with no derating required up to 70 °C — the current rating holds flat across the entire operating temperature range. Breaking capacity is specified by voltage: 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V. The 187 kA figure at 240 V is the headline number — it tells you this breaker can handle very high available fault current on a 240 V system without needing a current-limiting upstream device. At 690 V the 7.5 kA rating is lower, but that voltage is uncommon for motor branch circuits this breaker would typically protect. The part includes an undervoltage release (UVR) as the auxiliary release, plus a complement of auxiliary switches: 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch. A trip indicator is present on the front face for quick visual status on the panel door. Dimensions are 248 mm high, 138 mm wide, 110 mm deep. The 138 mm width is the standard 3-pole MCCB footprint for this SENTRON frame size — it occupies three adjacent 45 mm-wide DIN positions if panel-mounted on a mounting plate, or bolts directly into the enclosure backplane. Depth of 110 mm (4.33 in) leaves room behind a 200 mm-deep enclosure for wiring and the UVR coil connections. Maximum power loss is 40 W.","metaTitle":"Siemens 3VA2325-5MN32-0DL0 SENTRON MCCB, 250 A, 3-Pole, Moto","metaDescription":"Siemens SENTRON 3VA2325-5MN32-0DL0 molded case circuit breaker, 250 A rated at 40 °C, 3-pole, motor protection design with undervoltage release. Breaking capacity 187 kA at 240 V.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"17 s","Minimum":"4 s","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"7.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"250 A","at 60 °C":"250 A","at 65 °C":"250 A","at 70 °C":"250 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"40 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2325-5MN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"55 000 W","operating power / at AC-3 / at 400 V":"110 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=570005&mlfb=3VA2325-5MN32-0DL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-5MN32-0DL0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2325-5MN32-0DL0 at 240 V?","answer":"187 kA at 240 V. At 415 V and 440 V it is 121 kA, at 500 V it is 75.6 kA, and at 690 V it is 7.5 kA."},{"question":"Does 3VA2325-5MN32-0DL0 include an undervoltage release?","answer":"Yes, it includes an undervoltage release (UVR) as the auxiliary release, plus 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch."},{"question":"Where can I buy 3VA2325-5MN32-0DL0?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-5MN32-0DL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-5MN32-0DL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}