{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-6HL32-0BH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-6HL32-0BH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-6HL32-0BH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HL32-0BH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2325-6HL32-0BH0, molded case circuit breaker, 3-pole, 250 A continuous rating, 242 kA breaking capacity at 240 V, line protection design with undervoltage release and auxiliary switches.","salesMarkdown":"Its 3-pole construction and 242 kA breaking capacity at 240 V (187 kA at 415 V, 121 kA at 500 V, 7.5 kA at 690 V) mean it can interrupt fault currents up to those levels without upstream cascading, making it suitable for high-fault service-entrance or distribution positions where SCCR headroom is critical. The trip indicator confirms the breaker has opened on fault, a useful diagnostic for remote monitoring or panel walk-downs. ## Integration notes Mounts in a standard panel or enclosure — it is a DIN-rail-mountable MCCB (the SENTRON 3VA series uses a snap-on foot for 35 mm DIN rail). The undervoltage release (UVR) requires a separate control voltage; verify the coil rating matches the panel's control supply before wiring. Maximum power loss is 40 W at full rated current. That is modest for a 250 A frame, but in a densely packed panel with multiple breakers, the cumulative heat should be factored into the enclosure ventilation calculation.","metaTitle":"Siemens 3VA2325-6HL32-0BH0 SENTRON MCCB, 250 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2325-6HL32-0BH0 molded case circuit breaker, 250 A continuous, 3-pole, 242 kA breaking at 240 V. Current lifecycle. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"3 000 A","Minimum":"375 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"7.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"250 A","at 60 °C":"250 A","at 65 °C":"250 A","at 70 °C":"250 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"40 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2325-6HL32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB11","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=365061&mlfb=3VA2325-6HL32-0BH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HL32-0BH0/alternatives.json"},"ai":{"faq":[{"question":"What is the physical size of 3VA2325-6HL32-0BH0?","answer":"Height 248 mm, width 138 mm, depth 110 mm. The depth is the critical dimension for enclosure fit — verify clearance to the door and rear wiring gutter."},{"question":"Does 3VA2325-6HL32-0BH0 include auxiliary contacts?","answer":"Yes, it comes with 2 auxiliary switches plus 1 trip alarm switch HQ, and an undervoltage release (UVR) is built in."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-6HL32-0BH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-6HL32-0BH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}