{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-6HL32-0CC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-6HL32-0CC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-6HL32-0CC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HL32-0CC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, 3-pole molded case circuit breaker, 250 A rated continuous current Iu, 242 kA breaking capacity at 240 V, line protection version with ETU320 electronic trip unit, undervoltage release.","salesMarkdown":"## Siemens 3VA2325-6HL32-0CC0 — 250 A MCCB with 242 kA interrupting rating This SENTRON 3VA2325-6HL32-0CC0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current Iu of 250 A across the 40 °C to 50 °C band before derating begins at 55 °C. Breaking capacity hits 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 40 kA at 690 V — enough to handle high-fault utility feeds and transformer secondaries without cascading upstream. The 242 kA at 240 V and 187 kA at 415 V mean this breaker can sit at the main incoming position in a panel fed by a large transformer — a typical 2000 kVA transformer at 415 V can deliver around 140 kA prospective fault current, so this unit clears that with headroom. At 690 V the 40 kA rating still covers most industrial 690 V distribution. For selectivity coordination downstream, the ETU320 supports I²t-on and I²t-off modes to tune short-time delay against downstream 3VA breakers. At 55 °C it drops to 240 A, at 60 °C to 235 A, at 65 °C to 230 A, and at 70 °C to 225 A. The maximum power loss is 40 W — that heat must be managed inside the panel. ## Auxiliary and undervoltage release configuration The integrated auxiliary trip module is order code 3VA9608-0BB24. The base switch without auxiliaries is 3VA2325-6HL32-0AA0. No communication function, no phase failure detection, no ground fault monitoring — this is a plain line-protection breaker, not a power meter.","metaTitle":"Siemens 3VA2325-6HL32-0CC0 SENTRON MCCB, 250 A, 242 kA at 24","metaDescription":"Siemens 3VA2325-6HL32-0CC0 SENTRON 3-pole MCCB, 250 A rated, 242 kA breaking at 240 V, ETU320 release, undervoltage release included. Current production, available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"40 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"240 A","at 60 °C":"235 A","at 65 °C":"230 A","at 70 °C":"225 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"40 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"250 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2325-6HL32-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB24","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"250 A","Adjustable response value current / li max.":"3 000 A","Adjustable response value current / li min.":"375 A","Adjustable response value current / lr min.":"100 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"400 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"35 x 10","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=104169&mlfb=3VA2325-6HL32-0CC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HL32-0CC0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCCB at 415 V?","answer":"187 kA at 415 V and at 440 V, dropping to 121 kA at 500 V and 40 kA at 690 V. At 240 V the rating is 242 kA."},{"question":"Does 3VA2325-6HL32-0CC0 include an undervoltage release?","answer":"Yes, the auxiliary release is an undervoltage release (UVR) fitted as standard. Two auxiliary switches HQ are also included."},{"question":"Where can I buy 3VA2325-6HL32-0CC0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"Will 3VA2325-6HL32-0CC0 fit in a panel designed for a 3VA1112-5EF32-0CA0?","answer":"The 3VA2 frame size is physically larger than the 3VA1 — the 3VA2325-6HL32-0CC0 is 138 mm wide versus the 3VA1's narrower footprint, so it will not drop into the same mounting cutout or DIN-rail position without panel modification. The functional difference is also significant: this is a 250 A line-protection breaker with an ETU320 trip unit, while the 3VA1 is a smaller-frame device."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-6HL32-0CC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-6HL32-0CC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}