{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-6HL32-0CL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-6HL32-0CL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-6HL32-0CL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HL32-0CL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2325-6HL32-0CL0, molded case circuit breaker, 3-pole, 250 A rated continuous current, line protection design, 242 kA breaking capacity at 240 V AC.","salesMarkdown":"The Siemens SENTRON 3VA2325-6HL32-0CL0 is a 3-pole molded case circuit breaker (MCCB) rated for 250 A continuous current, designed for line protection in distribution panels and industrial switchgear. Its breaking capacity is 242 kA at 240 V AC, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 7.5 kA at 690 V — the 690 V figure is the limiting case for high-voltage low-fault applications, so verify the available fault current at your system voltage before specifying. The continuous current rating holds at 250 A across the full ambient range from 40 °C to 70 °C, meaning no derating is needed for elevated panel temperatures up to that limit. ## Auxiliary Switching and Release Configuration This MCCB is equipped with 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch (HQ type), plus an undervoltage release (UVR). A trip indicator is present for quick visual identification of a fault trip, and the breaker does not include a voltage trigger or communication function. ## Physical Integration and Environmental Limits Dimensions are 248 mm height, 138 mm width, and 110 mm depth — a standard 3-pole MCCB footprint that fits most Siemens SENTRON mounting bases and panel cutouts. Operating temperature range is -25 °C to 70 °C, with storage from -40 °C to 80 °C, covering most indoor industrial environments without special enclosures. Maximum power loss is 40 W, which should be factored into enclosure thermal calculations for densely populated panels.","metaTitle":"Siemens 3VA2325-6HL32-0CL0 SENTRON MCCB, 250 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2325-6HL32-0CL0 molded case circuit breaker, 250 A continuous, 3-pole, 242 kA breaking at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"3 000 A","Minimum":"375 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"7.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"250 A","at 60 °C":"250 A","at 65 °C":"250 A","at 70 °C":"250 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"40 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2325-6HL32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=18015&mlfb=3VA2325-6HL32-0CL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HL32-0CL0/alternatives.json"},"ai":{"faq":[{"question":"Does 3VA2325-6HL32-0CL0 include an undervoltage release?","answer":"Yes, it is equipped with an undervoltage release (UVR) as standard, along with 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-6HL32-0CL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-6HL32-0CL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}