{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-6HL32-0DH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-6HL32-0DH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-6HL32-0DH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HL32-0DH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2325-6HL32-0DH0, molded case circuit breaker, 3-pole, 250 A continuous rating, line protection design, 242 kA breaking capacity at 240 V.","salesMarkdown":"The interrupting capacity runs 242 kA at 240 V, drops to 187 kA at 415 V and 440 V, then 121 kA at 500 V, and 7.5 kA at 690 V — so the high fault-current headroom is at the lower voltages common in North American distribution, while the 690 V figure keeps it usable on 600 V class systems with moderate fault levels. The basic switch core is order code 3VA2325-6HL32-0AA0, so if you're swapping just the trip unit, that's the reference. The breaker measures 138 mm wide, 248 mm tall, and 110 mm deep — that's about 5.43 by 9.76 by 4.33 inches. ## Thermal and electrical limits Max power loss is 40 W at rated load — that's the heat you need to vent in a sealed enclosure. The trip indicator is present, and there's no voltage-trigger or communication function on this variant — it's a straight line-protection breaker with undervoltage release.","metaTitle":"Siemens 3VA2325-6HL32-0DH0 SENTRON MCCB, 250 A, 3-Pole","metaDescription":"Siemens SENTRON 3VA2325-6HL32-0DH0 molded case circuit breaker, 250 A continuous, 3-pole, 242 kA at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"3 000 A","Minimum":"375 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"7.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"250 A","at 60 °C":"250 A","at 65 °C":"250 A","at 70 °C":"250 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"40 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2325-6HL32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=423471&mlfb=3VA2325-6HL32-0DH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HL32-0DH0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2325-6HL32-0DH0?","answer":"Submit an RFQ against this order code. We source it to order and confirm current pricing and availability at quote time through our independent distribution network."},{"question":"Will 3VA2325-6HL32-0DH0 drop into a panel specified around 3VA2116-5HL32-0AK0?","answer":"Both are 3-pole SENTRON MCCBs in the same 3VA platform, so the mounting footprint and bus-bar spacing are the same. The 3VA2325-6HL32-0DH0 is a 250 A frame versus the 160 A frame of the 3VA2116-5HL32-0AK0 — check that your bus bars and lug kit are rated for 250 A before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-6HL32-0DH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-6HL32-0DH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}