{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-6HL32-0HA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-6HL32-0HA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-6HL32-0HA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HL32-0HA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2325-6HL32-0HA0, molded case circuit breaker, 3-pole, 250 A, line protection, ETU320 electronic trip unit, breaking capacity 242 kA at 240 V.","salesMarkdown":"The Siemens SENTRON 3VA2325-6HL32-0HA0 is a 3-pole molded case circuit breaker rated for 250 A continuous current (Iu) at 40 °C, with an ETU320 electronic overcurrent release. The breaking capacity is the headline: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 40 kA at 690 V. Those numbers tell you this breaker handles high-fault-current scenarios — transformer secondaries, large busway feeds, or industrial mains where available fault current runs high. The ETU320 release gives adjustable long-time, short-time, and instantaneous pickup, plus ground-fault alarm or trip if you add the optional module. At 55 °C it derates to 240 A, then 235 A at 60 °C, 230 A at 65 °C, and 225 A at 70 °C. The frame dimensions are 248 mm high, 138 mm wide, 110 mm deep — that's a standard 3VA2 frame footprint, so it drops into the same mounting holes and bus connections as other 3VA2 breakers in the 250 A class. ## What's inside the can The basic switch assembly carries order code 3VA2325-6HL32-0AA0. The integrated auxiliary trip is 3VA9688-0BL30 — that's the shunt trip coil that lets a remote signal or emergency-stop circuit open the breaker. The ETU320 release is field-configurable for LSI (long-time, short-time, instantaneous) protection curves.","metaTitle":"Siemens 3VA2325-6HL32-0HA0 SENTRON MCCB, 250 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2325-6HL32-0HA0 molded case circuit breaker, 250 A, 3-pole, line protection, ETU320 release, breaking capacity 242 kA at 240 V. Active production, sourced to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"40 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"240 A","at 60 °C":"235 A","at 65 °C":"230 A","at 70 °C":"225 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"37.5 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"250 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2325-6HL32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL30","Design of the overcurrent release":"ETU320","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"250 A","Adjustable response value current / li max.":"3 000 A","Adjustable response value current / li min.":"375 A","Adjustable response value current / lr min.":"100 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"400 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"35 x 10","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=336449&mlfb=3VA2325-6HL32-0HA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HL32-0HA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2325-6HL32-0HA0 and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a quote request; availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of 3VA2325-6HL32-0HA0 at different voltages?","answer":"242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 40 kA at 690 V."},{"question":"What trip unit does 3VA2325-6HL32-0HA0 use?","answer":"It uses the ETU320 electronic overcurrent release, providing adjustable LSI protection curves."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-6HL32-0HA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-6HL32-0HA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}