{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-6HL32-0JL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-6HL32-0JL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-6HL32-0JL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HL32-0JL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series, molded case circuit breaker, 3VA2325-6HL32-0JL0, 250 A continuous, 3-pole, 242 kA at 240 V, line protection design.","salesMarkdown":"The Siemens SENTRON 3VA2325-6HL32-0JL0 is a 3-pole molded case circuit breaker rated for 250 A continuous current across the full 40 °C to 70 °C ambient range — no derating needed up to that ceiling. Breaking capacity hits 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 7.5 kA at 690 V, so it handles high-fault utility feeds and transformer secondaries without cascading upstream. The basic switch variant underneath is 3VA2325-6HL32-0AA0. ## Breaking capacity and thermal performance That matters for panels packed into hot enclosures or near process heat. The 242 kA at 240 V is the headline interrupt rating; at 690 V it drops to 7.5 kA, which still covers most 690 V motor branch circuits. The 3-pole construction with shunt trip (STL) means it can be remotely tripped via a control signal, useful for emergency-stop integration or supervisory shutdown. ## Panel integration No communication module on board; this is a standalone line-protection breaker with voltage-trigger capability and a trip indicator. Maximum power loss is 37.5 W — factor into enclosure thermal calculations.","metaTitle":"Siemens SENTRON 3VA2325-6HL32-0JL0 MCCB, 250 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2325-6HL32-0JL0 molded case circuit breaker, 250 A continuous, 3-pole, 242 kA breaking at 240 V. Current production. Sourced to order — request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"3 000 A","Minimum":"375 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"7.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"250 A","at 60 °C":"250 A","at 65 °C":"250 A","at 70 °C":"250 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"37.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2325-6HL32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=37073&mlfb=3VA2325-6HL32-0JL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HL32-0JL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2325-6HL32-0JL0?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of 3VA2325-6HL32-0JL0 at 415 V?","answer":"187 kA at 415 V, matching the rating at 440 V."},{"question":"Does 3VA2325-6HL32-0JL0 include a shunt trip?","answer":"Yes, it ships with a shunt trip (STL) auxiliary release plus 2 auxiliary switches, 1 trip alarm switch, and 1 electrical alarm switch."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-6HL32-0JL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-6HL32-0JL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}