{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-6HN32-0AE0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-6HN32-0AE0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-6HN32-0AE0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HN32-0AE0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2325-6HN32-0AE0, molded case circuit breaker, 3-pole, 250 A continuous, interrupting 242 kA at 240 V, line protection design.","salesMarkdown":"The Siemens 3VA2325-6HN32-0AE0 is a SENTRON molded case circuit breaker (MCCB) rated for 250 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. Its 3-pole construction and interrupting capacity of 242 kA at 240 V, 187 kA at 415/440 V, 121 kA at 500 V, and 7.5 kA at 690 V suit it for high-fault utility feeds and large motor branch circuits in industrial switchgear. ## Integration & environment The breaker measures 248 mm high, 138 mm wide, and 110 mm deep — sized for standard MCCB panel cutouts. Operating temperature range spans -25 °C to 70 °C, with storage from -40 °C to 80 °C, so it handles unheated enclosures in cold storage or freezer-antechamber applications without condensation concerns. Maximum power loss is 37.5 W, which factors into enclosure thermal budgeting.","metaTitle":"Siemens 3VA2325-6HN32-0AE0 SENTRON MCCB, 250 A, 3-pole, 242","metaDescription":"Siemens 3VA2325-6HN32-0AE0 SENTRON molded case circuit breaker, 250 A continuous, 3-pole, interrupting up to 242 kA at 240 V. Active production. Sourced to order; request quote for","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"3 000 A","Minimum":"3 000 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"7.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"250 A","at 60 °C":"250 A","at 65 °C":"250 A","at 70 °C":"250 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"37.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2325-6HN32-0AA0","Design Of The Auxiliary Switch":"4 auxiliary switches HQ","Design Of The Auxiliary Release":"Without auxiliary release","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=215579&mlfb=3VA2325-6HN32-0AE0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HN32-0AE0/alternatives.json"},"ai":{"faq":[{"question":"What are the interrupting ratings for 3VA2325-6HN32-0AE0?","answer":"At 240 V it interrupts 242 kA; at 415 V and 440 V, 187 kA; at 500 V, 121 kA; and at 690 V, 7.5 kA."},{"question":"What is the continuous current rating of 3VA2325-6HN32-0AE0?","answer":"250 A continuous, with no derating required from 40 °C up to 70 °C ambient."},{"question":"How do I get current pricing and availability for 3VA2325-6HN32-0AE0?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm current pricing and availability."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-6HN32-0AE0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-6HN32-0AE0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}