{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-6HN32-0AG0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-6HN32-0AG0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-6HN32-0AG0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HN32-0AG0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, molded case circuit breaker, 3VA2325-6HN32-0AG0, 250 A, 3-pole, line protection, 242 kA at 240 V.","salesMarkdown":"It is a 3-pole unit rated for 250 A continuous current across the full ambient range from 40 °C up to 70 °C, meaning it carries the same 250 A without derating in a warm enclosure — a useful simplification for panel builders who want one ampacity number for the entire operating window. The interrupting ratings are substantial: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 7.5 kA at 690 V. Maximum rated current is 3 000 A, and the minimum is also 3 000 A — this is a fixed-rating frame, not an adjustable one. The breaker ships with a 250 A continuous rating, but the frame itself is the 3 000 A platform, which gives mechanical headroom for the high interrupting duty. The 110 mm depth is a key number for enclosure selection — it tells you the breaker projects 110 mm from the mounting surface, which determines the minimum enclosure depth needed to clear the door or deadfront. The auxiliary switch arrangement is factory-configured as 1 auxiliary + 1 trip alarm, which covers the common signaling needs for a line-side breaker — remote trip indication and breaker status.","metaTitle":"Siemens 3VA2325-6HN32-0AG0 SENTRON MCCB, 250 A, 3-Pole","metaDescription":"Siemens 3VA2325-6HN32-0AG0 SENTRON molded case circuit breaker, 250 A continuous, 3-pole, line protection. 242 kA at 240 V. Current lifecycle stage. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"3 000 A","Minimum":"3 000 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"7.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"250 A","at 60 °C":"250 A","at 65 °C":"250 A","at 70 °C":"250 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"37.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2325-6HN32-0AA0","Design Of The Auxiliary Switch":"1 auxiliary switch + 1 trip alarm switch HP","Design Of The Auxiliary Release":"Without auxiliary release","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB11","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=128654&mlfb=3VA2325-6HN32-0AG0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HN32-0AG0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting rating of 3VA2325-6HN32-0AG0 at 240 V?","answer":"242 kA at 240 V, which is a very high interrupting capacity suitable for service-entrance or high-fault-current positions."},{"question":"Where can I buy 3VA2325-6HN32-0AG0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-6HN32-0AG0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-6HN32-0AG0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}