{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-6HN32-0AJ0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-6HN32-0AJ0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-6HN32-0AJ0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HN32-0AJ0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2325-6HN32-0AJ0, molded case circuit breaker, 3-pole, 250 A continuous, 242 kA interrupting at 240 V, line protection design.","salesMarkdown":"The Siemens SENTRON 3VA2325-6HN32-0AJ0 is a 3-pole molded case circuit breaker rated 250 A continuous with a 3000 A frame — that frame size tells you the internal mechanism and contact structure are built for the full 3000 A interrupting duty, even though the continuous trip is set at 250 A. This matters for selectivity: you get the mechanical endurance and arc-chamber volume of a 3000 A frame while protecting a 250 A feeder. Interrupting capacity is where this part earns its place in a high-fault panel: 242 kA at 240 V, 187 kA at 415/440 V, 121 kA at 500 V, and 7.5 kA at 690 V. Maximum power loss is 37.5 W, which keeps the enclosure heat rise predictable for the guy laying out the gland plate and ventilation. ## Integration and footprint At 110 mm deep, 138 mm wide, and 248 mm tall, this MCCB fits the standard SENTRON 3VA2 panel footprint. The 138 mm width per 3-pole unit matches the typical DIN-rail or mounting-plate pitch in a distribution board — no surprises when you're laying out busbars or phase barriers. It is a straight line-protection breaker — the basic switch is order code 3VA2325-6HN32-0AA0. If you need those options, you step to a different suffix in the 3VA2 family.","metaTitle":"Siemens 3VA2325-6HN32-0AJ0 SENTRON MCCB, 250 A, 3-pole, 242","metaDescription":"Siemens SENTRON 3VA2325-6HN32-0AJ0 molded case circuit breaker, 250 A continuous, 3-pole, 242 kA interrupting at 240 V. Current lifecycle. Quoted to order. RFQ for availability and","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"3 000 A","Minimum":"3 000 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"7.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"250 A","at 60 °C":"250 A","at 65 °C":"250 A","at 70 °C":"250 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"37.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2325-6HN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HP","Design Of The Auxiliary Release":"Without auxiliary release","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB11","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=417862&mlfb=3VA2325-6HN32-0AJ0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HN32-0AJ0/alternatives.json"},"ai":{"faq":[{"question":"What auxiliary switches does this breaker include?","answer":"It comes with 2 auxiliary switches plus 1 trip alarm switch (HP type), giving two independent signal paths plus a dedicated fault-indicating contact."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-6HN32-0AJ0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-6HN32-0AJ0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}