{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-6HN32-0BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-6HN32-0BA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-6HN32-0BA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HN32-0BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2325-6HN32-0BA0, Molded case circuit breaker, 3-pole, 250 A, Line protection, ETU350 release, 242 kA at 240 V.","salesMarkdown":"The 3-pole form factor leaves room for side-mounted accessories. Undervoltage release (UVR) is built in — verify coil voltage matches your control circuit before wiring. ## Thermal derating and endurance Rated current holds at 250 A from 40 °C up to 50 °C, then steps down to 240 A at 55 °C, 235 A at 60 °C, 230 A at 65 °C, and 225 A at 70 °C (–). Mechanical endurance is 15,000 operations. Maximum power loss is 40 W — factor that into enclosure ventilation.","metaTitle":"Siemens 3VA2325-6HN32-0BA0 SENTRON MCCB, 250A, 3-Pole, 242kA","metaDescription":"Siemens SENTRON 3VA2325-6HN32-0BA0 molded case circuit breaker, 250A continuous, 3-pole, 242kA breaking at 240V. ETU350 release, undervoltage release. Active production. Quoted to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"40 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"240 A","at 60 °C":"235 A","at 65 °C":"230 A","at 70 °C":"225 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"No","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"Yes","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"40 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"250 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2325-6HN32-0AA0","Design of the auxiliary release":"Undervoltage release (UVR)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9608-0BB11","Design of the overcurrent release":"ETU350","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"0.5","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"250 A","Adjustable response value current / li max.":"3 000 A","Adjustable response value current / li min.":"3 000 A","Adjustable response value current / lr min.":"100 A","Adjustable response value current / Isd max.":"0 A","Adjustable response value current / Isd min.":"0 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"H","Max. rated operational current of the frame size":"400 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"35 x 10","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=406326&mlfb=3VA2325-6HN32-0BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HN32-0BA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2325-6HN32-0BA0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability."},{"question":"What is the breaking capacity of 3VA2325-6HN32-0BA0 at 240 V?","answer":"The breaking capacity is 242 kA at 240 V."},{"question":"What is the rated continuous current of this MCCB?","answer":"The rated continuous current Iu is 250 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-6HN32-0BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-6HN32-0BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}