{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-6HN32-0CH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-6HN32-0CH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-6HN32-0CH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HN32-0CH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2325-6HN32-0CH0, molded case circuit breaker, 3-pole, 250 A continuous, 242 kA breaking at 240 V, line protection, with undervoltage release and auxiliary switches.","salesMarkdown":"The Siemens SENTRON 3VA2325-6HN32-0CH0 is a 3-pole molded case circuit breaker (MCCB) rated for 250 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. That 250 A figure is the rated uninterrupted current, not a peak or short-time rating; it governs the conductor and bus sizing in the distribution panel. Breaking capacity is 242 kA at 240 V AC, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 7.5 kA at 690 V. The design is line protection, meaning it's optimized for feeder and main breaker duty rather than motor branch circuit protection. Power loss is rated at 40 W maximum, which matters for thermal management inside a sealed enclosure; that figure should be included in the panel's heat dissipation budget. Dimensions are 138 mm wide, 248 mm high, 110 mm deep. That provides two independent signal contacts for status feedback (e.g., open/closed) plus a dedicated alarm contact that changes state only on a fault trip — useful for remote annunciation without wiring through the main contacts. The storage limit is the handling limit — the breaker can be stored in unheated warehouses but must be within operating range when energized. No ground-fault monitoring version is fitted; this is a straight overcurrent/line protection device. If ground-fault protection is required, a separate module or a different variant would be needed.","metaTitle":"Siemens 3VA2325-6HN32-0CH0 SENTRON MCCB, 250 A, 3-pole, 242","metaDescription":"Siemens SENTRON 3VA2325-6HN32-0CH0 molded case circuit breaker, 250 A continuous, 3-pole, 242 kA breaking at 240 V. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"3 000 A","Minimum":"3 000 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"7.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"250 A","at 60 °C":"250 A","at 65 °C":"250 A","at 70 °C":"250 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"40 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2325-6HN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=463733&mlfb=3VA2325-6HN32-0CH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HN32-0CH0/alternatives.json"},"ai":{"faq":[{"question":"What is 3VA2325-6HN32-0CH0's listed depth (110 mm) on this component line?","answer":"The depth is 110 mm, which is the dimension from the mounting surface to the rear of the breaker body — relevant for enclosure depth clearance."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-6HN32-0CH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-6HN32-0CH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}