{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-6HN32-0CL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-6HN32-0CL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-6HN32-0CL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HN32-0CL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2325-6HN32-0CL0, molded case circuit breaker, 3-pole, 250 A continuous, 242 kA breaking at 240 V, line protection, undervoltage release.","salesMarkdown":"The Siemens SENTRON 3VA2325-6HN32-0CL0 is a 3-pole molded case circuit breaker rated for 250 A continuous current at 40 °C, with a maximum breaking capacity of 242 kA at 240 V and 187 kA at 415 V. For a 250 A frame, those are high-end ratings — you'd see these in heavy industrial switchboards with large transformer feeds or motor control centers where fault currents can exceed 100 kA. ## Thermal derating and continuous current That's unusual for an MCCB; most frames start dropping current above 40 °C. It means you can pack this breaker into a warm enclosure or mount it next to other heat sources without recalculating the load. ## Auxiliary and alarm switching This variant ships with two auxiliary switches plus a trip alarm and an electrical alarm switch (HQ type). That gives you remote status: one set for breaker open/closed, one for tripped vs healthy, and one for electrical fault. The HQ alarm switch is typically wired into a PLC input or annunciator panel so a trip event triggers an immediate alarm without waiting for a polling cycle.","metaTitle":"Siemens 3VA2325-6HN32-0CL0 SENTRON MCCB, 250 A, 3-Pole, 242","metaDescription":"Siemens SENTRON 3VA2325-6HN32-0CL0 molded case circuit breaker, 250 A continuous, 3-pole, 242 kA breaking at 240 V. Line protection with undervoltage release. Active production, so","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"3 000 A","Minimum":"3 000 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"7.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"250 A","at 60 °C":"250 A","at 65 °C":"250 A","at 70 °C":"250 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"40 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2325-6HN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=371735&mlfb=3VA2325-6HN32-0CL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6HN32-0CL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2325-6HN32-0CL0 and how do I get a price?","answer":"This part is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — no stock figures or lead-time numbers are published here."},{"question":"What is 3VA2325-6HN32-0CL0's listed depth?","answer":"The depth is 110 mm (4.33 in)."},{"question":"What is 3VA2325-6HN32-0CL0's listed width?","answer":"The width is 138 mm (5.43 in)."},{"question":"What compliance documentation does this breaker carry?","answer":"The evidence does not list specific compliance marks (UL, CSA, CE, IEC) for this order code. Typical SENTRON MCCBs carry IEC 60947-2 and UL 489 certifications; verify the specific markings on the nameplate or request the manufacturer's declaration for your jurisdiction."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-6HN32-0CL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-6HN32-0CL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}