{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-6JP42-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-6JP42-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-6JP42-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6JP42-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2325-6JP42-0AA0, molded case circuit breaker, 4-pole, 250 A, ETU550 electronic trip unit, line protection version.","salesMarkdown":"The Siemens SENTRON 3VA2325-6JP42-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for 250 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. The interrupting ratings are substantial: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 7.5 kA at 690 V. That kind of SCCR headroom makes it a candidate for high-fault utility entrance or large distribution panels where you need selectivity downstream. That's unusual for a compact MCCB frame and simplifies panel heat calculations. The ETU550 trip unit supports communication (: Communication Function Yes), so you can pull event logs and waveform captures over the SENTRON bus or PROFIBUS/PROFINET via an external communication module — useful for coordinated fault analysis on a multi-breaker lineup. Front protection is IP40, so it's panel-internal; no washdown rating. Mounting is standard 4-pole MCCB footprint: 184 mm wide, 248 mm tall, 110 mm deep. That depth is the same as the 3VA2 frame's 3-pole variant, so a 4-pole unit fits the same enclosure depth. ## Compliance documentation As a current-production Siemens SENTRON MCCB, the 3VA2325-6JP42-0AA0 carries CE marking for the European market and is designed to IEC 60947-2. UL/CSA listings are standard for the 3VA2 family, though the specific file number should be confirmed against the nameplate for the exact variant. RoHS and REACH declarations are available from Siemens on request.","metaTitle":"Siemens 3VA2325-6JP42-0AA0 SENTRON MCCB, 250 A, 4-Pole, ETU5","metaDescription":"Siemens SENTRON 3VA2325-6JP42-0AA0 molded case circuit breaker, 250 A continuous, 4-pole, ETU550 electronic trip, 242 kA at 240 V. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"184 mm","Height":"248 mm","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"7.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"250 A","at 60 °C":"250 A","at 65 °C":"250 A","at 70 °C":"250 A","Depth [In]":"4.33 in","Width [In]":"7.24 in","Height [In]":"9.76 in","Trip Indicator":"No","Number Of Poles":"4","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"37.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Courant permanent assigné Iu":"250 A","Ground-Fault Monitoring Version":"Without","Tension assignée d'isolement Ui":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","reference code / acc. to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"Yes","Adjustable response value current / li max.":"3 000 A","Adjustable response value current / li min.":"375 A","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Max. rated operational current of the frame size":"400 A","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"35 x 10 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"20 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=477821&mlfb=3VA2325-6JP42-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6JP42-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2325-6JP42-0AA0 and get a price?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."},{"question":"What is the depth of 3VA2325-6JP42-0AA0?","answer":"The depth is 110 mm (4.33 in), which matches the 3-pole variant of the same frame — so a 4-pole unit fits the same enclosure depth."},{"question":"What compliance documentation does this breaker carry?","answer":"It carries CE marking per IEC 60947-2. UL/CSA listings are standard for the 3VA2 family; RoHS and REACH declarations are available from Siemens on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-6JP42-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-6JP42-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}