{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-6KP32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-6KP32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-6KP32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6KP32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, molded case circuit breaker, 3VA2325-6KP32-0AA0, 250 A, 3-pole, ETU850 electronic trip unit, line protection design.","salesMarkdown":"The Siemens 3VA2325-6KP32-0AA0 is a SENTRON 3VA2-series molded case circuit breaker rated for 250 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. It is a 3-pole unit designed for line protection, fitted with the ETU850 electronic trip unit. Breaking capacity reaches 242 kA at 240 V and 187 kA at 415 V and 440 V, stepping down to 121 kA at 500 V and 7.5 kA at 690 V. The ETU850 release supports communication and additional measurement functions, so it feeds power-quality data back to a BMS or PLC — not just a dumb overcurrent trip. Dimensions are 248 mm high, 138 mm wide, 110 mm deep — a standard 3-pole MCCB footprint for 250 A frame size. The adjustable overcurrent release range spans 375 A to 3 000 A — that is the magnetic/instantaneous pickup window, not the continuous rating. The continuous rating is fixed at 250 A; the ETU850 lets you dial in the short-circuit and short-time pickup within that band for selective coordination downstream. As a SENTRON 3VA2 product, this MCCB is designed and tested to IEC 60947-2 and carries the associated CE marking for European markets. RoHS and REACH compliance documentation is standard from Siemens for the 3VA series. No UL or CSA listing is confirmed in the available data — verify with the full datasheet if UL 489 listing is required for your jurisdiction.","metaTitle":"Siemens 3VA2325-6KP32-0AA0 SENTRON MCCB, 250 A, ETU850, 3-Po","metaDescription":"Siemens 3VA2325-6KP32-0AA0 SENTRON molded case circuit breaker, 250 A continuous, 3-pole, ETU850 electronic trip unit. Active production. Breaking capacity 242 kA at 240 V. Availab","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"3 000 A","Minimum":"375 A","at 240 V":"242 kA","at 415 V":"187 kA","at 440 V":"187 kA","at 500 V":"121 kA","at 690 V":"7.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"250 A","at 60 °C":"250 A","at 65 °C":"250 A","at 70 °C":"250 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"37.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"H","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=433995&mlfb=3VA2325-6KP32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-6KP32-0AA0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-6KP32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-6KP32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}