{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-7HL32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-7HL32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-7HL32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-7HL32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2325-7HL32-0AA0, molded case circuit breaker, 3-pole, 250 A, line protection, ETU320 overcurrent release, breaking capacity 330 kA at 240 V.","salesMarkdown":"The 3VA2325-7HL32-0AA0: The 250 A continuous rating holds across the full ambient temperature range from 40 °C to 70 °C — no derating needed up to that ceiling, which simplifies panel sizing in warm enclosures. The 800 V rated insulation voltage (Ui) confirms the breaker can be applied in 480/277 V and 600 V systems with margin. Dimensions are 248 mm height, 138 mm width, 110 mm depth, fitting standard Siemens 3VA mounting patterns and busbar systems.","metaTitle":"Siemens 3VA2325-7HL32-0AA0 SENTRON MCCB, 250 A, 3-Pole, ETU3","metaDescription":"Siemens SENTRON 3VA2325-7HL32-0AA0 molded case circuit breaker, 250 A continuous, 3-pole, ETU320 release. Breaking capacity up to 330 kA at 240 V. Active production, sourced to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"3 000 A","Minimum":"375 A","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"7.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"250 A","at 60 °C":"250 A","at 65 °C":"250 A","at 70 °C":"250 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"37.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=302414&mlfb=3VA2325-7HL32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-7HL32-0AA0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-7HL32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-7HL32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}