{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-7HM32-0AC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-7HM32-0AC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-7HM32-0AC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-7HM32-0AC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA2 IEC frame 400 circuit breaker, 3-pole, breaking capacity class C, Icu=110kA @ 415V, line protection ETU330, LIG, In=250A, overload Ir=100A...250A, short-circuit Ii=1.5...12 x In, ground-fault Ig=0.2...1 x In, tg=0.1/0.3s, with nut keeper kit and 2 auxiliary switches HQ.","salesMarkdown":"Its ETU330 trip unit with LIG (long-time, instantaneous, ground) functions covers In=250A, with overload pickup adjustable from 100A to 250A and short-circuit pickup from 1.5 to 12 times In. Ground-fault protection is settable from 0.2 to 1 times In with a time delay of 0.1 or 0.3 seconds. The nut keeper kit secures the breaker in place during high-vibration environments. Two auxiliary switches HQ are factory-fitted, providing status feedback for remote monitoring or PLC inputs — useful for a maintenance technician verifying breaker position without opening the panel door.","metaTitle":"Siemens 3VA2325-7HM32-0AC0 Circuit Breaker, 250A, 110kA @ 41","metaDescription":"Siemens 3VA2325-7HM32-0AC0 IEC frame 400 circuit breaker, 3-pole, 250A, Icu=110kA @ 415V, ETU330 LIG protection. Current lifecycle stage. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1093250&mlfb=3VA2325-7HM32-0AC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-7HM32-0AC0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2325-7HM32-0AC0?","answer":"The rated ultimate breaking capacity Icu is 110 kA at 415 V, class C per IEC 60947-2, meaning it can safely interrupt fault currents up to that level."},{"question":"What protection functions does the ETU330 trip unit provide?","answer":"The ETU330 provides LIG protection: long-time overload (Ir adjustable 100A...250A), instantaneous short-circuit (Ii adjustable 1.5...12 x In), and ground-fault (Ig adjustable 0.2...1 x In with time delay 0.1 or 0.3 s)."},{"question":"Where can I buy 3VA2325-7HM32-0AC0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-7HM32-0AC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-7HM32-0AC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}