{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-7MN32-0JA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-7MN32-0JA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-7MN32-0JA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-7MN32-0JA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON molded case circuit breaker, 3VA2325-7MN32-0JA0, 3-pole, motor protection, 250 A rated continuous current, ETU350M electronic overcurrent release, shunt trip, breaking capacity 330 kA at 240 V.","salesMarkdown":"## MCCB with motor protection and high breaking capacity It is equipped with an ETU350M electronic overcurrent release and an integrated shunt trip (STL) auxiliary release. Breaking capacity is rated per voltage: 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 52.5 kA at 690 V. Rated continuous current holds at 250 A from 40 °C through 50 °C ambient, then derates to 240 A at 55 °C, 235 A at 60 °C, 230 A at 65 °C, and 225 A at 70 °C. Minimum operating temperature is -25 °C; maximum is 70 °C. Maximum power loss is 37.5 W. ## Integration and mounting dimensions Panel cutout dimensions: width 138 mm, height 248 mm, depth 110 mm. The 3-pole form factor fits standard Siemens SENTRON mounting bases. No auxiliary contacts are fitted as standard; the auxiliary contact version is listed as without.","metaTitle":"Siemens 3VA2325-7MN32-0JA0 SENTRON MCCB, 250 A, 3-Pole, Moto","metaDescription":"Siemens 3VA2325-7MN32-0JA0 SENTRON molded case circuit breaker, 250 A rated continuous current, 3-pole, motor protection with ETU350M release. Breaking capacity 330 kA at 240 V. Ac","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"52.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"240 A","at 60 °C":"235 A","at 65 °C":"230 A","at 70 °C":"225 A","Trip indicator":"No","Number of poles":"3","Product version":"Motor protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Power loss [W] / maximum":"37.5 W","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"250 A","Rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA2325-7MN32-0AA0","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"ETU350M","Protection class IP / on the front":"IP40","Operating power / at AC-3 / at 400 V":"110 W","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"17","Adjustable response value time / tr min.":"4","Adjustable response value time / tsd max.":"0.03 s","Adjustable response value time / tsd min.":"0.03 s","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"Yes","Adjustable response value current / Ir max.":"250 A","Adjustable response value current / li max.":"3 750 A","Adjustable response value current / li min.":"3 750 A","Adjustable response value current / lr min.":"100 A","Adjustable response value current / Isd max.":"3 750 A","Adjustable response value current / Isd min.":"750 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LSI","Switching capacity class of the circuit breaker":"C","Max. rated operational current of the frame size":"400 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"Lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569861&mlfb=3VA2325-7MN32-0JA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-7MN32-0JA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2325-7MN32-0JA0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of 3VA2325-7MN32-0JA0 at 415 V?","answer":"The breaking capacity is 242 kA at 415 V."},{"question":"What overcurrent release does 3VA2325-7MN32-0JA0 use?","answer":"It uses an ETU350M electronic overcurrent release, designed for motor protection applications."},{"question":"Will 3VA2325-7MN32-0JA0 fit a panel cutout for a 3VA1110-5EE32-0JA0?","answer":"The 3VA2325-7MN32-0JA0 is a different frame size (250 A vs. the 3VA1110 series lower current range); dimensions differ, so it will not drop into the same cutout without panel modification."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-7MN32-0JA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-7MN32-0JA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}