{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2325-7MN32-0KH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2325-7MN32-0KH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2325-7MN32-0KH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2325-7MN32-0KH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2325-7MN32-0KH0, molded case circuit breaker, 3-pole, 250 A (flat derating to 70 °C), 330 kA at 240 V, motor-protection design, shunt trip, auxiliary switches.","salesMarkdown":"The Siemens 3VA2325-7MN32-0KH0 is a SENTRON molded case circuit breaker (MCCB) in a motor-protection design, rated 250 A continuously from 40 °C through 70 °C with no derating step across that band — unusual for a 250 A frame, and a strong signal that the thermal-magnetic or electronic trip assembly is oversized relative to the continuous current, so it holds full rating in a warm enclosure. Breaking capacity is 330 kA at 240 V, 242 kA at 415 V and 440 V, 187 kA at 500 V, and 7.5 kA at 690 V — these are the SCCR values the breaker can interrupt without welding its contacts or venting arc gas into the panel, so the 242 kA at 415 V covers most industrial 400 V distribution boards, and the 7.5 kA at 690 V is the limit for 690 V motor circuits. Phase failure detection is included, which matters for motor protection: if one phase drops out on the line side, the breaker trips rather than letting the motor single-phase and overheat. ## Mechanical footprint and panel integration The 110 mm depth is the projection behind the panel face — relevant when fitting into a shallow enclosure or a multi-row distribution board where rear clearance is tight. ## Lifecycle and compliance posture Maximum power loss 37.5 W — a figure to include in enclosure thermal calculations if the breaker is in a sealed cabinet with other dissipating devices.","metaTitle":"Siemens 3VA2325-7MN32-0KH0 SENTRON MCCB, 250 A, 3-Pole","metaDescription":"Siemens SENTRON 3VA2325-7MN32-0KH0 molded case circuit breaker, 250 A rated at 40 °C, 3-pole, 330 kA at 240 V. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"17 s","Minimum":"4 s","at 240 V":"330 kA","at 415 V":"242 kA","at 440 V":"242 kA","at 500 V":"187 kA","at 690 V":"7.5 kA","at 40 °C":"250 A","at 45 °C":"250 A","at 50 °C":"250 A","at 55 °C":"250 A","at 60 °C":"250 A","at 65 °C":"250 A","at 70 °C":"250 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Motor protection","Communication Function":"No","Phase Failure Detection":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"37.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2325-7MN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"250 A","Insulation Voltage / Rated Value":"800 V","adjustable trip class (Tc CLASS)":"10A, 10E, 20E","Design Of The Overcurrent Release":"ETU350M","protection class IP / on the front":"IP40","operating power / at AC-3 / at 230 V":"55 000 W","operating power / at AC-3 / at 400 V":"110 000 W","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"C","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ad4b9644ff5db6bf2edb958ed105bffe.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=569867&mlfb=3VA2325-7MN32-0KH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2325-7MN32-0KH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2325-7MN32-0KH0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."},{"question":"What is the depth of 3VA2325-7MN32-0KH0?","answer":"The depth is 110 mm."},{"question":"What is the width of 3VA2325-7MN32-0KH0?","answer":"The width is 138 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2325-7MN32-0KH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2325-7MN32-0KH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}