{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2340-5HL32-0HC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2340-5HL32-0HC0","canonicalUrl":"https://aoctrl.com/siemens/3VA2340-5HL32-0HC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2340-5HL32-0HC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2340-5HL32-0HC0, molded case circuit breaker, 3-pole, 400 A continuous, 187 kA breaking capacity at 240 V AC, line protection design with shunt trip and 2 auxiliary switches.","salesMarkdown":"The Siemens SENTRON 3VA2340-5HL32-0HC0 is a 3-pole molded case circuit breaker rated for 400 A continuous at 40 °C, with a breaking capacity of 187 kA at 240 V AC. At 415 V and 440 V it still holds 121 kA, and at 500 V it's 75.6 kA. This is a line-protection device — meaning it's designed for feeder and main breaker duty, not motor branch-circuit protection. The continuous current holds flat at 400 A from 40 °C through 50 °C, then derates to 385 A at 55 °C, 370 A at 60 °C, 355 A at 65 °C, and 340 A at 70 °C. The max power loss is 96 W — account for that in your panel thermal budget if the breaker is enclosed in a small cabinet with other heat sources. ## Built-in accessories and what they do for commissioning No undervoltage release is fitted; if you need UVR protection, that's a different variant. The breaker has a voltage trigger (shunt trip) but no trip indicator and no communication function. It's a standalone device — no Modbus or PROFIBUS module inside. For remote monitoring you'd add an external I/O block reading the auxiliary contacts. That's a standard SENTRON 3VA2 frame size.","metaTitle":"Siemens 3VA2340-5HL32-0HC0 SENTRON MCCB, 400 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2340-5HL32-0HC0 molded case circuit breaker, 400 A continuous, 3-pole, 187 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"4 000 A","Minimum":"600 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"7.5 kA","at 40 °C":"400 A","at 45 °C":"400 A","at 50 °C":"400 A","at 55 °C":"385 A","at 60 °C":"370 A","at 65 °C":"355 A","at 70 °C":"340 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"96 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2340-5HL32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"400 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU320","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL30","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c1b3b6c5f6d67465025ac41848ceb75e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=76355&mlfb=3VA2340-5HL32-0HC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2340-5HL32-0HC0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of this MCCB at 240 V?","answer":"It is rated 187 kA at 240 V AC. At 415 V and 440 V it is 121 kA, at 500 V it is 75.6 kA, and at 690 V it is 7.5 kA."},{"question":"What is the continuous current rating and how does it derate with temperature?","answer":"The continuous current is 400 A from 40 °C to 50 °C. It derates to 385 A at 55 °C, 370 A at 60 °C, 355 A at 65 °C, and 340 A at 70 °C."},{"question":"What accessories are built into this breaker?","answer":"It includes a shunt trip release (STL) for remote tripping and two HQ auxiliary switches for status feedback. There is no undervoltage release and no communication module."},{"question":"Where can I buy 3VA2340-5HL32-0HC0 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2340-5HL32-0HC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2340-5HL32-0HC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}