{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2340-5HN32-0JL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2340-5HN32-0JL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2340-5HN32-0JL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2340-5HN32-0JL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, molded case circuit breaker, 3VA2340-5HN32-0JL0, 400 A, 3-pole, line protection, 187 kA interrupting at 240 V.","salesMarkdown":"## What this 3VA2 MCCB carries The Siemens SENTRON 3VA2340-5HN32-0JL0 is a 3-pole molded case circuit breaker rated for 400 A continuous current — no derating needed up to 50 °C, where it still holds the full 400 A. Above that, it steps down in 15 °C increments: 385 A at 55 °C, 370 A at 60 °C, 355 A at 65 °C, and 340 A at 70 °C. That thermal curve is what you use for panel sizing, not the nameplate number. Interrupting capacity runs 187 kA at 240 V, drops to 121 kA at 415 V and 440 V, then 75.6 kA at 500 V, and 7.5 kA at 690 V. It's a standard SENTRON 3VA2 footprint, so if you've got a 3VA2 frame in the panel already, this drops into the same mounting pattern. As a SENTRON 3VA2 series MCCB, it carries the usual Siemens compliance package — UL 489, IEC 60947-2, CSA C22.2 No. 5. RoHS and REACH declarations are available with the product documentation. The basic switch variant is 3VA2340-5HN32-0AA0 if you need the core breaker without the auxiliary switch package.","metaTitle":"Siemens SENTRON 3VA2340-5HN32-0JL0 MCCB, 400 A, 3-Pole","metaDescription":"Siemens SENTRON 3VA2340-5HN32-0JL0 molded case circuit breaker, 400 A continuous, 187 kA interrupting at 240 V. Active production. Sourced to order. RFQ for pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"4 000 A","Minimum":"4 000 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"7.5 kA","at 40 °C":"400 A","at 45 °C":"400 A","at 50 °C":"400 A","at 55 °C":"385 A","at 60 °C":"370 A","at 65 °C":"355 A","at 70 °C":"340 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"96 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2340-5HN32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"400 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU350","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c1b3b6c5f6d67465025ac41848ceb75e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=2505&mlfb=3VA2340-5HN32-0JL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2340-5HN32-0JL0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of this MCCB?","answer":"187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V."},{"question":"What are the physical dimensions of 3VA2340-5HN32-0JL0?","answer":"248 mm high, 138 mm wide, and 110 mm deep."},{"question":"How do I get pricing and availability for this breaker?","answer":"Submit an RFQ through this listing. Current pricing and stock are confirmed at quote time through independent distribution channels."},{"question":"What auxiliary switches come with this breaker?","answer":"It carries 2 auxiliary switches plus 1 trip alarm switch and 1 electrical alarm switch, with a shunt trip release (STL)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2340-5HN32-0JL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2340-5HN32-0JL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}