{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2340-5JP32-0AF0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2340-5JP32-0AF0","canonicalUrl":"https://aoctrl.com/siemens/3VA2340-5JP32-0AF0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2340-5JP32-0AF0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2340-5JP32-0AF0, molded case circuit breaker, 3-pole, 400 A rated continuous current, line protection design, breaking capacity 187 kA at 240 V AC, with communication function and integrated auxiliary switch + trip alarm.","salesMarkdown":"## What this 3VA2340-5JP32-0AF0 is and what it carries It's the communication-enabled variant of the base switch 3VA2340-5JP32-0AA0, adding a communication function for remote monitoring or integration into a higher-level control system. Breaking capacity is the headline here: 187 kA at 240 V AC, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V. Above that, it derates linearly: 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C. Dimensions: 248 mm height, 138 mm width, 110 mm depth. ## Auxiliary contacts and communication No undervoltage release or shunt trip is included — those would be added as external modules if needed. The communication function is onboard, so this breaker can report status and trip events over a bus system without an add-on gateway.","metaTitle":"Siemens 3VA2340-5JP32-0AF0 SENTRON MCCB, 400A, 3-Pole, 187kA","metaDescription":"Siemens SENTRON 3VA2340-5JP32-0AF0 molded case circuit breaker, 400A continuous, 3-pole, breaking capacity 187kA at 240V AC. Active production, sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","title":"3VA2340-5JP32-0AF0","Height":"248 mm","Maximum":"4 000 A","Minimum":"600 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"7.5 kA","at 40 °C":"400 A","at 45 °C":"400 A","at 50 °C":"400 A","at 55 °C":"375 A","at 60 °C":"350 A","at 65 °C":"325 A","at 70 °C":"300 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","description":"circuit breaker 3VA2 IEC frame 400 breaking capacity class M Icu=55kA @ 415V 3-pole, line protection ETU550, LSI, In=400A overload protection Ir=160A...400A short-circuit protection Isd=0.6...10 x In, Ii=1.5 x In N conductor protection optionally with external current transformer, up to 160% nut keeper kit 1 auxiliary switch HQ 1 trip alarm switch HQ","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"96 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2340-5JP32-0AA0","Design Of The Auxiliary Switch":"1 auxiliary switch + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"Without auxiliary release","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"400 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c1b3b6c5f6d67465025ac41848ceb75e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=157456&mlfb=3VA2340-5JP32-0AF0"},"ai":{"faq":[{"question":"Where can I buy 3VA2340-5JP32-0AF0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the breaking capacity of 3VA2340-5JP32-0AF0 at different voltages?","answer":"Breaking capacity is 187 kA at 240 V AC, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V."},{"question":"Does 3VA2340-5JP32-0AF0 have communication capability?","answer":"Yes, it includes a communication function for remote monitoring and integration with control systems."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2340-5JP32-0AF0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2340-5JP32-0AF0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}