{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2340-5JP32-0KA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2340-5JP32-0KA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2340-5JP32-0KA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2340-5JP32-0KA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2340-5JP32-0KA0, molded case circuit breaker, 3-pole, 400 A continuous, line protection, shunt trip release, 110 x 138 x 248 mm.","salesMarkdown":"The Siemens SENTRON 3VA2340-5JP32-0KA0 is a 3-pole molded case circuit breaker rated for 400 A continuous current, designed for line protection in distribution panels. ## Breaking capacity and SCCR The interrupting ratings span the voltage range: 187 kA at 240 V, 121 kA at both 415 V and 440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V. ## Thermal derating The breaker holds its full 400 A rating from 40 °C up to 50 °C. Above that, it derates linearly: 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C. If your panel ambient runs hot — say, a packed enclosure with drives — plan for that 300 A floor at 70 °C rather than the nameplate 400 A. ## Physical fit and mounting Dimensions are 248 mm high, 138 mm wide, and 110 mm deep.","metaTitle":"Siemens 3VA2340-5JP32-0KA0 SENTRON MCCB, 400 A, 3-Pole","metaDescription":"Siemens SENTRON 3VA2340-5JP32-0KA0 molded case circuit breaker, 400 A continuous, 3-pole, line protection. SCCR 187 kA at 240 V. Shunt trip release. Current lifecycle. Quoted to or","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"4 000 A","Minimum":"600 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"7.5 kA","at 40 °C":"400 A","at 45 °C":"400 A","at 50 °C":"400 A","at 55 °C":"375 A","at 60 °C":"350 A","at 65 °C":"325 A","at 70 °C":"300 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"96 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2340-5JP32-0AA0","Design Of The Auxiliary Switch":"Without","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"400 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU550","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c1b3b6c5f6d67465025ac41848ceb75e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=131675&mlfb=3VA2340-5JP32-0KA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2340-5JP32-0KA0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA2340-5JP32-0KA0 at 240 V?","answer":"The interrupting rating is 187 kA at 240 V, which covers high-fault scenarios common on transformer secondaries or large busway feeds."},{"question":"Where can I buy 3VA2340-5JP32-0KA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2340-5JP32-0KA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2340-5JP32-0KA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}