{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2340-5JQ32-0AH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2340-5JQ32-0AH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2340-5JQ32-0AH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2340-5JQ32-0AH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2340-5JQ32-0AH0, molded case circuit breaker, 3-pole, 400 A, line protection, interrupting 187 kA at 240 V, 121 kA at 415 V, with communication function and trip indicator.","salesMarkdown":"Above that, the thermal curve steps down: 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C — so a panel running at 60 °C ambient loses 50 A of headroom. The interrupting capacity is the headline: 187 kA at 240 V, 121 kA at both 415 V and 440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V. The adjustable trip range spans 600 A minimum to 4 000 A maximum, with an initial value of 80 A and full-scale of 400 A — the electronic trip unit is field-configurable for coordination studies. No undervoltage release or other auxiliary release is fitted on this variant, so if undervoltage protection is needed, specify the release separately. Power loss is 96 W maximum at rated current — factor that into enclosure ventilation calculations.","metaTitle":"Siemens SENTRON 3VA2340-5JQ32-0AH0 MCCB, 400 A, 3-Pole, 187","metaDescription":"Siemens SENTRON 3VA2340-5JQ32-0AH0 molded case circuit breaker, 400 A, 3-pole, interrupting 187 kA at 240 V. Line protection, communication function, trip indicator. Sourced to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"4 000 A","Minimum":"600 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"7.5 kA","at 40 °C":"400 A","at 45 °C":"400 A","at 50 °C":"400 A","at 55 °C":"375 A","at 60 °C":"350 A","at 65 °C":"325 A","at 70 °C":"300 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Initial Value":"80 A","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Full-Scale Value":"400 A","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"96 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2340-5JQ32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"Without auxiliary release","Ground-Fault Monitoring Version":"Summation current formation L-conductor","Continuous Current / Rated Value":"400 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU560","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Product Function / Grounding Protection":"Yes","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSIG","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c1b3b6c5f6d67465025ac41848ceb75e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=501528&mlfb=3VA2340-5JQ32-0AH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2340-5JQ32-0AH0/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3VA2340-5JQ32-0AH0?","answer":"Submit an RFQ through this listing. The part is sourced to order through independent distribution; pricing and stock are confirmed at quote time."},{"question":"What is 3VA2340-5JQ32-0AH0's interrupting capacity at 240 V?","answer":"It interrupts 187 kA at 240 V, which is the highest rating on this breaker — suitable for high-fault-current distribution panels."},{"question":"Does 3VA2340-5JQ32-0AH0 include a communication function?","answer":"Yes, this variant includes a communication function for remote monitoring and integration with a control system."},{"question":"What compliance documentation is available for this breaker?","answer":"The SENTRON 3VA series typically carries UL, CSA, CE, and IEC certifications. Specific documentation (declaration of conformity, RoHS/REACH) is provided with the shipment or available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2340-5JQ32-0AH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2340-5JQ32-0AH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}