{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2340-5JQ32-0CL0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2340-5JQ32-0CL0","canonicalUrl":"https://aoctrl.com/siemens/3VA2340-5JQ32-0CL0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2340-5JQ32-0CL0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 series, molded case circuit breaker, 3VA2340-5JQ32-0CL0, 3-pole, 400 A (40 °C), adjustable thermal-magnetic trip 600–4000 A, interrupting capacity 187 kA at 240 V AC.","salesMarkdown":"It's a 3-pole unit with an adjustable thermal-magnetic trip unit covering 600 A to 4000 A, and a continuous current rating of 400 A at 40 °C. The interrupting capacity hits 187 kA at 240 V AC, dropping to 121 kA at 415/440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V — so it handles high-fault utility feeds and transformer secondaries without cascading upstream. This breaker holds 400 A continuously from 40 °C up to 50 °C, then derates linearly: 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C. The 110 mm depth, 138 mm width, and 248 mm height fit standard MCCB mounting footprints; the 98.5 W max power loss means ventilation slots or forced air above 60 °C ambient are worth planning for. That covers remote status, trip indication, and undervoltage protection without adding external relays. The basic switch variant is 3VA2340-5JQ32-0AA0 — this -0CL0 suffix adds the UVR and communication function.","metaTitle":"Siemens 3VA2340-5JQ32-0CL0 SENTRON MCCB, 400 A, 600-4000 A T","metaDescription":"Siemens 3VA2340-5JQ32-0CL0 SENTRON molded case circuit breaker, 3-pole, 400 A rated at 40 °C, adjustable trip 600-4000 A, 187 kA at 240 V. Current lifecycle stage. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"4 000 A","Minimum":"600 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"7.5 kA","at 40 °C":"400 A","at 45 °C":"400 A","at 50 °C":"400 A","at 55 °C":"375 A","at 60 °C":"350 A","at 65 °C":"325 A","at 70 °C":"300 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Initial Value":"80 A","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Full-Scale Value":"400 A","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"98.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA2340-5JQ32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch + 1 electrical alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Summation current formation L-conductor","Continuous Current / Rated Value":"400 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU560","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"Yes","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSIG","number of CO contacts / for auxiliary contacts":"4","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB22","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c1b3b6c5f6d67465025ac41848ceb75e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=226408&mlfb=3VA2340-5JQ32-0CL0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2340-5JQ32-0CL0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA2340-5JQ32-0CL0 and what is the lead time?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number published here."},{"question":"What are the key ratings for this MCCB?","answer":"3-pole, 400 A continuous at 40 °C, adjustable thermal-magnetic trip 600–4000 A, interrupting capacity 187 kA at 240 V AC, 121 kA at 415/440 V, 75.6 kA at 500 V, 7.5 kA at 690 V."},{"question":"What is the physical size of 3VA2340-5JQ32-0CL0?","answer":"Depth 110 mm, width 138 mm, height 248 mm."},{"question":"Does this breaker include communication capability?","answer":"Yes, the communication function is listed as present on this variant."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2340-5JQ32-0CL0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2340-5JQ32-0CL0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}