{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2340-5KP32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2340-5KP32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2340-5KP32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2340-5KP32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2340-5KP32-0AA0, molded case circuit breaker, 3-pole, 400 A continuous, ETU850 electronic trip unit, line protection design, with communication function.","salesMarkdown":"Above 55 °C the curve steps down: 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C. That means if your panel ambient runs 55 °C or higher, the breaker's effective rating drops — size the load accordingly or plan for forced ventilation. Breaking capacity is 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V. At 690 V the 7.5 kA rating is lower, so verify your system's prospective short-circuit current at that voltage level before specifying. Three-pole design, line protection configuration, and IP40 on the front face. Dimensions: 248 mm height, 138 mm width, 110 mm depth. That 138 mm width is the 3-pole footprint — it fits standard SENTRON 3VA mounting plates and busbar systems. Depth of 110 mm means it clears most shallow enclosures, but check gland-plate clearance if you're back-paneling with a rear cover. The ETU850 includes a communication function — that means it can talk to a higher-level system (PROFIBUS, PROFINET, or Modbus via the SENTRON communication modules) for remote trip indication, current monitoring, and parameter adjustment. No undervoltage release and no voltage trigger on this variant; ground-fault monitoring is also absent. If you need those, look at the 3VA2 options with the appropriate suffix.","metaTitle":"Siemens 3VA2340-5KP32-0AA0 SENTRON MCCB, 400 A, 3-Pole, ETU8","metaDescription":"Siemens SENTRON 3VA2340-5KP32-0AA0 molded case circuit breaker, 400 A continuous, 3-pole, ETU850 trip unit. Breaking capacity 187 kA at 240 V. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"4 000 A","Minimum":"600 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"7.5 kA","at 40 °C":"400 A","at 45 °C":"400 A","at 50 °C":"400 A","at 55 °C":"375 A","at 60 °C":"350 A","at 65 °C":"325 A","at 70 °C":"300 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"96 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"400 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c1b3b6c5f6d67465025ac41848ceb75e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=501191&mlfb=3VA2340-5KP32-0AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2340-5KP32-0AA0/alternatives.json"},"ai":{"faq":[{"question":"Does 3VA2340-5KP32-0AA0 include a communication function?","answer":"Yes, the ETU850 trip unit supports communication — it can interface with SENTRON communication modules for remote monitoring and parameterization."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2340-5KP32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2340-5KP32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}