{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2340-5KP32-0BA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2340-5KP32-0BA0","canonicalUrl":"https://aoctrl.com/siemens/3VA2340-5KP32-0BA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2340-5KP32-0BA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2 molded case circuit breaker, 3VA2340-5KP32-0BA0, 400 A continuous, 3-pole, line protection with undervoltage release, 187 kA at 240 V.","salesMarkdown":"## 400 A MCCB with a wide interrupting-capacity envelope ## Interrupting capacity — what the voltage columns tell you This breaker delivers 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V. The steep drop above 500 V means the 690 V rating governs any high-voltage bus application; for most 400 V-class industrial feeds the 121 kA figure provides substantial fault-current headroom. Above that, the breaker derates linearly: 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C. The 138 mm width matches the common 3-pole molded-case breaker slot; verify the bus-bar drilling pattern against the existing panel cutout.","metaTitle":"Siemens 3VA2340-5KP32-0BA0 SENTRON MCCB, 400 A, 3-Pole, 187","metaDescription":"Siemens 3VA2340-5KP32-0BA0 SENTRON molded case circuit breaker, 400 A continuous, 3-pole, 187 kA interrupting at 240 V. Current lifecycle. Available to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"4 000 A","Minimum":"600 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"7.5 kA","at 40 °C":"400 A","at 45 °C":"400 A","at 50 °C":"400 A","at 55 °C":"375 A","at 60 °C":"350 A","at 65 °C":"325 A","at 70 °C":"300 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"98.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Of The Supplied Basic Switch":"3VA2340-5KP32-0AA0","Design Of The Auxiliary Switch":"Without","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"400 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB11","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c1b3b6c5f6d67465025ac41848ceb75e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=399757&mlfb=3VA2340-5KP32-0BA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2340-5KP32-0BA0/alternatives.json"},"ai":{"faq":[{"question":"Does this MCCB include an undervoltage release?","answer":"Yes, it is fitted with an undervoltage release (UVR) as standard, allowing remote tripping by dropping the control voltage."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2340-5KP32-0BA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2340-5KP32-0BA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}