{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA2340-5KP32-0BH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA2340-5KP32-0BH0","canonicalUrl":"https://aoctrl.com/siemens/3VA2340-5KP32-0BH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA2340-5KP32-0BH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA2340-5KP32-0BH0, molded case circuit breaker, 3-pole, 400 A continuous, interrupting rating 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 500 V.","salesMarkdown":"The Siemens SENTRON 3VA2340-5KP32-0BH0 is a 3-pole molded case circuit breaker rated for 400 A continuous current, with a maximum frame rating of 4 000 A and a minimum trip setting of 600 A. It's designed for line protection in distribution panels, with interrupting capacity that varies by voltage: 187 kA at 240 V, 121 kA at both 415 V and 440 V, 75.6 kA at 500 V, and 7.5 kA at 690 V. Thermal derating is published from 40 °C through 70 °C: it holds full 400 A up to 50 °C, then drops to 375 A at 55 °C, 350 A at 60 °C, 325 A at 65 °C, and 300 A at 70 °C. The trip indicator is standard, and there's no ground-fault monitoring built in — that's external if needed. Dimensions: 248 mm height, 138 mm width, 110 mm depth. That's a 3-pole frame that fits standard switchboard or panelboard cutouts — no odd footprint. The 110 mm depth means it clears shallow enclosures where deeper MCCBs would hit the backplate or gland plate.","metaTitle":"Siemens 3VA2340-5KP32-0BH0 SENTRON MCCB, 400 A, 3-pole, 187","metaDescription":"Siemens SENTRON 3VA2340-5KP32-0BH0 molded case circuit breaker, 400 A continuous, 3-pole, 187 kA SCCR at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"110 mm","Width":"138 mm","Height":"248 mm","Maximum":"4 000 A","Minimum":"600 A","at 240 V":"187 kA","at 415 V":"121 kA","at 440 V":"121 kA","at 500 V":"75.6 kA","at 690 V":"7.5 kA","at 40 °C":"400 A","at 45 °C":"400 A","at 50 °C":"400 A","at 55 °C":"375 A","at 60 °C":"350 A","at 65 °C":"325 A","at 70 °C":"300 A","Depth [In]":"4.33 in","Width [In]":"5.43 in","Height [In]":"9.76 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"Yes","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"98.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"Yes","Of The Supplied Basic Switch":"3VA2340-5KP32-0AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"400 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"ETU850","protection class IP / on the front":"IP40","design of the N-conductor protection":"adjustable OFF; 20% to 160%","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB11","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"400 A","Product Extension / Optional / Motor Drive":"Yes","Protection Function Of The Overcurrent Release":"LSI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"M","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"on both sides nut keeper kit","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c1b3b6c5f6d67465025ac41848ceb75e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=396102&mlfb=3VA2340-5KP32-0BH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA2340-5KP32-0BH0/alternatives.json"},"ai":{"faq":[{"question":"Will 3VA2340-5KP32-0BH0 drop into a panel specified around 3VA2116-5JP32-0AE0 without rewiring?","answer":"The 3VA2340 frame is physically larger (248 x 138 x 110 mm vs the 3VA2116's smaller frame). It will not drop into the same cutout or bus connection without panel rework — this is a higher-current frame, not a direct mechanical swap."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA2340-5KP32-0BH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA2340-5KP32-0BH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}